期刊文献+

北京某商业建筑温湿度独立控制空调系统的全年能耗分析 被引量:4

Energy Consumption Analysis of the Whole Year for a Commercial Building with Temperature and Humidity Independent Control Air-conditioning System in Beijing
在线阅读 下载PDF
导出
摘要 以北京某一商业建筑为模拟对象,对其空调冷负荷进行模拟,并在此基础上计算普通空调系统和温湿度独立控制空调系统的能耗。经过对能耗的比较和分析表明,温湿度独立控制空调系统的能耗比普通空调系统的能耗降低了16.4%,冷水机组全年平均性能系数提高了13%。结果表明温湿度独立控制空调系统具有很好的应用前景。 The air-conditioning cooling load of a commercial building is simulated by DEST in Beijing. And the energy consumption values are calculated respectively for ordinary air conditioning system and temperature and humidity independent control air-conditioning system (THAS). Compared with the ordinary .systems, THAS can achieve savings about 16.4% on the power consumption. In addition, the aceroge coefficient of chiller performonce (COP) can increase about 13% the whole year. The result sows that THAS has better application prospects.
出处 《建筑节能》 CAS 2009年第12期21-23,33,共4页 BUILDING ENERGY EFFICIENCY
基金 深圳市科技局资助项目 太阳能溶液蓄能除湿空调系统研究(08KJfc013)
关键词 空调系统 温湿度独立控制 能耗分析 air-conditioning system independent control on temperature and humidity energy consumption analysis