汶川地震中变电站开关设备破坏机理 被引量:12

Seismic Failure Analysis on Substation Switch Equipments in Wenchuan Earthquake
在线阅读 下载PDF
导出
摘要 目的分析汶川大地震中大量遭受破坏的变电站电气设备的地震易损性和震害机理.方法通过建立软母线连接的变电站开关设备耦联体系的有限元分析模型,采用非线性的索单元模拟软母线的作用.在实际记录的汶川地震波输入下,对耦联体系有限元模型进行了地震时程分析,对比了结构地震响应计算结果.结果隔离开关有母线连接瓷柱和无母线连接瓷柱的响应差别很大,母线对设备的响应影响是比较大的,它是导致设备发生破坏的重要原因.由于母线的存在,母线连接设备体系的结构响应呈现非线性的特点.结论变电站电气设备是典型的地震易损结构,在设备的抗震分析中需要考虑母线的耦联作用. Many substation equipments were damaged during Wenchuan Earthquake, May 12th, 2008. In order to analyze seismic vulnerability and failure mechanism, finite element model of substation switch equipments interconnected by flexible bus was established, in which the cable element was used to simulate the flexible bus. Under the input of recorded Wenchuan Earthquake ground motions, time history analysis was made and the seismic responses were compared using the FEM model. The results show that the structural responses of the bus connected equipments are different from that of the independent equipments, which indicates that the influence of flexible bus on equipments cannot be ignored. Tension transmission through the flexible bus is one of the main reasons to cause seismic failure of some equipment and it should be considered in the seismic design of substation equipments interconnected by flexible bus.
作者 谢强 王亚非
出处 《沈阳建筑大学学报(自然科学版)》 CAS 北大核心 2009年第6期1050-1057,共8页 Journal of Shenyang Jianzhu University:Natural Science
基金 教育部霍英东教育基金会优选资助课题(114021) 国家电网公司科技项目(SGKJJSKF2008-508)
关键词 变电站设备 汶川地震 破坏机理 有限元分析 substation equipments Wenchuan Earthquake failure mechanism finite element analysis
  • 相关文献

参考文献13

  • 1于永清.四川电网汶川地震电力设施受灾调研分析.电网技术,2008,32(11):1-6.
  • 2谢强.5.12汶川大地震电力系统震害调查初步报告[R].上海:同济大学,2008,8.
  • 3Okada T, Misaki T, Hashimoto Y. et al. Seismic design of connecting leads in open-air type substations [ C ]. Proc. Int. Conf. Large High Voltage Electric Systems, France : Paris, 1986.
  • 4Dastous J B. Design methodology for flexible bus- work between substation equipment subjected to earthquakes[ J]. IEEE Transactions on Power Deliery ,2007,22 ( 3 ) : 1490 - 1497.
  • 5IEEE power engineering society. IEEE1527 -2006 Recommended practice for the design of flexible bus- work located in seismically active areas [S ]. USA: The Institute of Electrical and Electronics Engineers, Inc. ,2006.
  • 6Ghalibafian H, Bhuyan G S, Ventura C, et al. Seismic behavior of flexible conductors connecting substation equipment-Part II : Shake table tests[J].IEEE Transactions on Power Delivery, 2004, 19 ( 4 ) : 1680 - 1687.
  • 7Filiatrault A, Stearns C. Electrical substation equipment interaction-experimental flexible conductor studies[ R ]. California: University of California, 2003.
  • 8Song J, Armen D K, Sackman J L. Seismic interaction in electrical substation equipment connected by non-linear rigid bus conductors [J ]. Earthquake Engineering and Structural Dynamics, 2007,36 : 167 - 190.
  • 9Armen D K, Sackman J L, Hong K J. Interaction in interconnected electrical substation equipment subjec- ted to earthquake ground motions[R]. California : University of California, 1999.
  • 10IEEE power engineering society. IEEE 693 - 2005 Recommended practice for seismic design of substations [ S ]. New York: The Institute of Electrical and Electronics Engineers, Inc. ,2006.

共引文献39

同被引文献147

引证文献12

二级引证文献69

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部