期刊文献+

一种自动捕风通风装置性能的实验研究 被引量:2

Experimental research of an air catcher's performance
在线阅读 下载PDF
导出
摘要 利用搭建的简易开放式通风实验台,实验研究了所研制的一种具有自动捕风功能的通风装置的最小启动风速、反应时间等机械性能及通风性能。结合北京地区2008年1,2月室外风速、风向实测数据,得到了北京地区冬季65%以上的时间都可以利用这种自动捕风通风装置实现建筑房间的无动力或微动力通风换气,从而达到节能目的的综合评估结果。 Studies the mechanical performance such as minimum start-up air speed, reaction time and ventilation performance of the catcher developed by the authors on the simple opening ventilation test-bed. Combined with the measured data of the wind speed and direction during the January and February 2008 in Beijing, obtains the integrated evaluation result that this air catcher can be used to realize the building ventilation without or with a little driving power more than 65% time in the winter of Beijing and achieve the aim of energy saving.
机构地区 北京工业大学
出处 《暖通空调》 北大核心 2009年第10期85-89,共5页 Heating Ventilating & Air Conditioning
基金 国家自然科学基金资助项目(编号:50678006)
关键词 自动捕风通风装置 无动力通风 机械性能 通风性能 实验 air catcher, ventilation without power, mechanical performance, ventilation performance, experiment
  • 相关文献

参考文献6

  • 1Harris D J, Webb R S. Wind towers-old technology to solve a new problem[C]// The 17th AIVC Conference: Optimum Ventilation and Air Flow Control in Buildings. Gothernhurg, Sweden, 1996: 613-621.
  • 2Bansal N K, Mathur R, Bhandari M S. A study of solar chimney assisted wind tower system for natural ventilation in buildings [J]. Renewable Energy, 1994, 29(4):495-500.
  • 3Elmualim A A, Awib H B, Teekaram A J, et al. Evaluating the performance of a windeatcher system using wind tunnel testing[C]//22nd Annual AIVC Conference, Bath, UK, AIVC, Air Infiltration and Ventilation Centre, INIVEEIG, Balguim, 2001.
  • 4郭春信.风帽的合理设计可强化地下空间自然通风[J].地下空间,1994,14(1):33-37. 被引量:6
  • 5李宏军,李晓锋,朱颖心,等.高大空间风压通风简化模拟方法研究[C]∥全国暖通空调制冷2004年学术文集.北京:中国建筑工业出版社,2004:71-75.
  • 6Li Zhiyuan, Chen Chao. Preliminary study on air flow characteristics of a new automatic wind catcher [C]//The 1st International Conference on Building Energy and Environment. Dalian, China, 2008.

共引文献5

同被引文献15

  • 1郭春信.风帽的合理设计可强化地下空间自然通风[J].地下空间,1994,14(1):33-37. 被引量:6
  • 2李宏军,李晓锋,朱颖心,等.高大空间风压通风简化模拟方法研究[C]∥全国暖通空调制冷2004年学术文集.北京:中国建筑工业出版社,2004:71-75.
  • 3ELMUALIM A A. Eect of damper and heat source on wind catcher natural ventilation performance[J]. Energy and Build- ings, 2006, 38(8): 939-948.
  • 4AWBI H B, ELMUALIM A A. Full scale model windeateher performance evaluation using a wind tunnelpC]//Proceedlngs of the World Renewable Energy Congress VII. Cologne, Ger- many, 2002.
  • 5HUGHES B R, ABDUL-GHANI S A A. Investigation of a windvent passive ventilation device against current fresh air supply recommendations [J]. Energy and Buildings, 2008, 40,1651-1659.
  • 6LI Zhi-yuan, CHEN Chao, HUO Liaoran. Numerical simula- tion and experimental study of a new type of automatic wind catcher[C]//6th International Symposium on HVAC. Nan- jing:Jiangsu Association of Refrigeration, 2009: 1307-1314.
  • 7霍廖然,陈超,薛亚宁,等.一种自动捕风装置排风特性的实验研究[c]//全国暖通空调制冷20lO年学术论文集.杭州.中国建筑学会暖通空调专业委员会,中国制冷学会空调热泵专业委员会,20lO:55.
  • 8厉松,任慧忠,李云龙.住宅式中央新风系统的应用研究[J].节能,2012,31(4):38-42. 被引量:9
  • 9符颢,梁卫辉,秦孟昊.华东地区不同通风形式下住宅室内挥发性有机化合物浓度及暴露量模拟分析[J].建筑科学,2016,32(8):20-26. 被引量:12
  • 10冯国会,姜编,黄凯良,张亿先,杨雪.严寒地区通风房间室内甲醛污染物浓度分布规律研究[J].流体机械,2017,45(11):79-84. 被引量:12