期刊文献+

变风量空调系统送风温度优化及容错控制 被引量:8

Optimal and Fault Tolerant Control of Supply Air Temperature in VAV Systems
在线阅读 下载PDF
导出
摘要 针对变风量空调(VAV)系统提出了基于湿度控制的送风温度优化及容错控制方法.该方法可以满足ASHRAE标准62-2001对室内空气品质和湿度的新要求,并提出了主成分分析、联合角度分析和故障补偿法则,该法则可以分别用于空调系统故障的检测、诊断和重构,从而实现对变风量空调系统的容错,保证系统优化目标的实现.在变风量空调系统的仿真器上进行了基于湿度控制的送风温度优化以及多种故障下的检测和诊断试验. Supply air temperature optimal and the corresponding fault tolerant control methods for VAV systems were presented. This method can satisfy the higher demand of indoor air quality and humidity strictly required in ASHRAE Standard 62-2001. Moreover, the principal component analysis, joint angle analysis and compensatory reconstruction methods were used to detect, identify and reconstruct the fault respectively so as to achieve the target of fault tolerant and optimal control of the VAV systems. The proposed methods were tested and evaluated in the VAV simulator.
出处 《上海交通大学学报》 EI CAS CSCD 北大核心 2009年第6期962-966,共5页 Journal of Shanghai Jiaotong University
基金 中国博士后基金资助项目(20070410179)
关键词 变风量空调系统 故障检测与诊断 容错 送风温度优化 室内湿度控制 variable air volume(VAV) air conditioning systems fault detection and diagnosis fault tolerants supply air temperature optimal indoor humidity control
  • 相关文献

参考文献11

  • 1Ann B C, Mitchell J W, Mclntosh L B. Model-based fault detection and diagnosis for cooling towers[J]. ASHRAE Transactions, 2001, 107(1) : 839-846.
  • 2Liu X F, Dexter A. Fault-tolerant supervisory control of VAV air-conditioning systems[J]. Energy and Buildings, 2001, 33(4): 379-389.
  • 3Yu B, van Paassen A H C, Riahy S. General modeling for model-based FDD on building HVAC systems [J]. Simulation Practice and Theory, 2002, 9 (6-8) : 387-397.
  • 4House J M, Vaezi-Nejad H, Whitcomb J M. An expert rules set for fault detection in air handling units/ discussion[J]. ASHRAE Transactions, 2001, 107 (1) : 858-871.
  • 5Wang S W, Chen Y M. Fault-tolerant control for outdoor ventilation air flow rate in building based on neural network[J]. Building and Environment, 2002, 37(7) : 691-704.
  • 6Lee W Y, House J M, Shin D R. Fault diagnosis and temperature sensor recovery for an air-handling unit [J]. ASHRAE Transactions, 1997, 103(1): 621-633.
  • 7Dexter A L, Ngo D. Fault diagnosis in HVAC systems: A multi-step fuzzy model-based approach[J]. HVAC&R Research,2001, 7(1) : 83-102.
  • 8ASHRAE Standard 62-2001, Fundamentals of good indoor air quality[S].
  • 9孙勇,晋欣桥,杜志敏,孙金龙.变风量空调系统室内湿度控制分析[J].上海交通大学学报,2005,39(2):216-219. 被引量:5
  • 10晋欣桥,孙金龙,杜志敏.变风量空调系统中基于预测的末端再热控制策略[J].上海交通大学学报,2006,40(2):316-319. 被引量:6

二级参考文献9

共引文献7

同被引文献64

引证文献8

二级引证文献30