1000kV同塔双回线路不平衡度及换位方式分析 被引量:52

Analysis on Unbalance Factor and Transposing Modes for 1000 kV Double-Circuit Transmission Lines on the Same Tower
原文传递
导出
摘要 对1000kV淮南-皖南同塔双回线路参数、母线电压和发电机电流的不平衡度进行了分析,研究中考虑了2种常用的换位方式,对不同换位方式下的潜供电流和恢复电压、感应电压和感应电流进行了比较。结果表明,从降低母线电压和发电机电流不平衡度的角度来看,采用换位方式2较好;从减少潜供电流和感应电压的角度来看,采用换位方式1更佳。在满足国标要求的前提下,为了限制线路的潜供电流、感应电压和感应电流,推荐淮皖线采用换位方式1。 The unbalance factors of line parameters, bus voltages and generator currents of 1 000 kV power doublecircuit transmission line on the same tower from Huainan to Wannan are analyzed. Two kinds of transposing modes in common use are taken into account. The secondary-arc currents and recovery voltages, induced voltages and induced currents under different transposing modes are compared. Comparison results show that from the viewpoint of reducing unbalance factors of bus voltage and generator currents, the transposing mode 2 is better; however, from the viewpoint of reducing secondary-arc currents and induced voltage, the transposing mode 1 is more suitable. Under the presupposition of satisfying the requirement given by national standard, to suppress the secondary-arc current, induced voltage and induced current of transmission line, it is recommended to adopt the transposing mode 1 in 1 000 kV transmission line from Huainan to Wannan.
出处 《电网技术》 EI CSCD 北大核心 2009年第5期1-5,16,共6页 Power System Technology
关键词 同塔双回线路 不平衡度 换位方式 潜供电流 感应电压 double-circuit transmission lines on the sametower unbalance factor transposing mode secondary-arccurrent induced voltage