摘要 500 kV干式空心电抗器用来限制500 kV系统的短路电流。在制造电抗器前,需要对电抗器的过电压耐受进行评估,保证匝间电压小于绝缘值。笔者在已知电抗器分布参数的基础上,用链型回路等值电抗器,采用PSCAD/EMTDC程序求解在雷电和操作冲击下的匝间电压。计算表明,雷电时外圈首匝匝间过电压最大,可达19.8 kV,操作时首匝匝间过电压最大,可达10 kV,但都小于36 kV的耐受值。 Air-cored current-limiting inductor (CLI) is used to limit the magnitude of fault current in 500 kV power systems. Before manufacturing the CLI, the over-voltage withstand ability of CLI should be evaluated to ensure the voltage between two coils less than the withstand value. Therefore, the distribution circuit of CLI is solved with PSCAD/EMTDC based on the known distribution parameter of CLI in this paper. The results show that the maximum voltage between the two first coils under lightning surge is 19.8 kV, and under switching is 10 kV, both of which are less thafi the withstand value 36 kV.
出处 《高压电器》 CAS CSCD 北大核心 2009年第1期11-14,共4页 High Voltage Apparatus
基金 自然科学基金项目(50737001)资助
关键词 500 kV限流电抗器 分布参数电路 过电压耐受 500kV current-limiting inductor distribution circuit over-vohage withstand
  • 相关文献

参考文献4

二级参考文献6

  • 1祝瑞金 杨增辉.华东500 kV电网短路电流抑制措施的研究[Z].,..
  • 2DRY TYPE AIR CORE REACTORS:Evolution of Technology. Trench Group.
  • 3Con Edison System Fault Current Management Plan, Presentation at the NYISO joint TPAS/IITF meeting, Octorber 4,2001.
  • 4Australasia news: ABB installs its largest series reactor at TransGrid's Sydney South 330 kV Substation.
  • 5SCCL-Short-Circuit Current Limitation with FACTS in High-Voltage Systems: Application & Features_V2 PTD HI6-H 1 PD/Re.
  • 6Accepted Bulk Power Series Reactor Applications on the PJM System.

共引文献49

同被引文献102

引证文献7

二级引证文献106

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部