期刊文献+

桐乡市城市污水处理厂对丝状菌污泥膨胀的控制实践 被引量:4

Control of Filamentous Sludge Bulking in Tongxiang Wastewater Treatment Plant
在线阅读 下载PDF
导出
摘要 介绍了桐乡市城市污水处理厂丝状菌污泥膨胀的处理对策,对发生污泥膨胀时的水质特点、工况条件进行分析,认为此次丝状菌污泥膨胀主要是由于低污泥负荷率、低溶解氧引起的。通过调整泥龄、污泥负荷、DO等运行参数,投加NaC lO溶液杀灭丝状菌等措施成功控制了此次污泥膨胀,可供同行参考。 The treatment countermeasures against the filamentous sludge bulking in Tongxiang Wastewater Treatment Plant are introduced. The wastewater quality characteristics and operation conditions during sludge bulking are analyzed. It is believed that the filamentous sludge bulking is caused by low sludge loading rate and low DO. It is effectively controlled by adjusting sludge age, mainly sludge loading and DO level, adding NaCIO to kill filamentous bacteria and so on, which provides reference for the designers.
出处 《中国给水排水》 CAS CSCD 北大核心 2008年第22期95-97,共3页 China Water & Wastewater
关键词 污泥膨胀 污泥负荷 丝状菌 NACLO sludge bulking sludge loading filamentous bacteria NaClO
  • 相关文献

参考文献3

二级参考文献16

  • 1王凯军.统一的活性污泥丝状菌型膨胀理论[J].环境科学,1993,14(2):44-48. 被引量:11
  • 2刘培,张雁秋.污泥膨胀特性与控制对策[J].水科学与工程技术,2006(4):37-38. 被引量:1
  • 3Ekama G A,Wentzel M C,Casey T G,et al.Filamentous organisms bulking in nutrient removal activated sludge system. Paper6: Review evaluation and consolidation of results. Water SA,1996,22(2):147~152
  • 4Gabriel B. Wastewater microbiology.New York:Ralph Mitchell.A John Wiley &Sons Inc.,1992.167~187
  • 5Jenkins D,Richard M G,Daigge G T.Manual on the causes and control of activated sludge bulking and foaming.South Africa:Water Research commission,Pretoria, 1984.236~243
  • 6Seviour E M,Williams C J, Seviour R J,et al.A survey of filamentous bacteria populations from foaming activated sludge plants in Eastern states of Australia. Water Res., 1984,24:493~498
  • 7Jiri Wanner. The implementation of bulking control in the design of activated sludge systems[J]. Water Science and Technology, 1994,29(7): 193-202.
  • 8Yamamoto-Ikemoto Ryoko, Matsui Saburo, Komori Tomoaki, et al. Control of filamentous bulking and interactions among sulfur oxidation- reduction and iron oxidation-reduction in activated sludge using an iron eoagulant[J]. Water Science and Technology, 1998,38 (8-9) :9-17.
  • 9Eikelboom D H, Grovenstein J. Control of bulking in a full scale plant by addition of talc (PE 8418) [J]. Water Science and Technology, 1998,37(4-5): 297-301.
  • 10Goar W Ramirez , Jose L Alonso, Adelina Villanueva. A rapid, direct method for assessing chlorine effect on filamentous bacteria in activated sludge[J]. Water Research, 2000, 34 (15): 3894-3898.