500/220kV同塔四回线路的耐雷性能研究 被引量:27

Lightning Performance of Quadruple-circuit Transmission Line with Dual Voltage 500/220kV on the Same Tower
在线阅读 下载PDF
导出
摘要 为准确评估500/220 kV同塔混压四回输电线路的耐雷性能,在采用改进电气几何模型(EGM)与电磁暂态程序(EMTP/ATP)计算其绕、反击跳闸率后分析了避雷线保护角、杆塔呼称高度、地面倾角等对5002、20 kV线路绕击耐雷性能的不同影响及杆塔呼称高度、接地电阻、耦合地线架设方式等对500、220 kV线路反击耐雷水平的不同影响。计算结果表明,同塔混压四回线路中不同电压等级线路防雷击侧重点不同,即500 kV线路绕击相对严重,220 kV线路反击相对严重。最后提出了改善线路雷电性能、降低雷击跳闸率的措施,在实际工程中,建议从降低杆塔呼称高度、采用负保护角以及架设耦合地线等方面综合考虑。 The lightning performance of quadruple-circuit transmission line with dual voltage 500/220 kV on the same tower is calculated and analyzed with EGM (Electro-geometrical Model) and EMTP (Elector-Magnetic Transient Program). And the effects of fielding angle, nominal height of the tower, ground elevation, grounding resistance and the way of laying additional shield wires are discussed in detail. In accordance with 500 kV and 220 kV transmission lines on the same tower , the results show that the priority is different for improving lightning performance, namely,the shielding failure is relatively serious for 500 kV transmission line,and the back flashover is relatively serious for 220 kV transmission line. Finally, several special methods that may be used to improve or degrade lightning performance are presented , such as reducing nominal height of the tower , using negative fielding angle and setting up additional shield wires.
出处 《高电压技术》 EI CAS CSCD 北大核心 2008年第10期2075-2080,共6页 High Voltage Engineering
基金 江苏省电力公司2007年重点科研项目(J2007029)~~
关键词 500/220KV 同塔四回线路 耐雷性能 电气几何模型 电磁暂态程序 雷击跳闸 500/220 kV quadruple-circuit transmission line on the same tower lightning performance EGM EMTP lightning outage
  • 相关文献

参考文献15

二级参考文献56

共引文献290

同被引文献236

引证文献27

二级引证文献178

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部