期刊文献+

电压切换回路的隐患分析 被引量:23

Hidden trouble analysis of voltage switch circuit
在线阅读 下载PDF
导出
摘要 双母线接线方式下的主变和线路操作箱中都设有电压切换回路。电压切换继电器同时动作将会引起PT二次并列并烧毁PT二次保险,从而使全站保护装置失压的现象;双重故障下,甚至造成全站失压,扩大事故范围的严重后果。针对电压切换回路中存在的这种隐患,本文进行了详细的分析探讨,并提出了一些相应措施,以提高电压切换回路的可靠性以及变电站运行的可靠性。 Voltage switch circuits are set in the operation boxes of transformers and transmission lines for duplicate bus scheme. The PT secondary circuit will be paralleled and the PT secondary safety device may be fused while the voltage switch relays operate at one time, which will make the protection devices of the whole transformer substation voltage loss. Furthermore, the whole transformer substation may lose voltage under another fault. For the existing hidden trouble of the voltage switch circuit, the detailed analysis is made in this paper. Also, some corresponding measures are brought forth, which can improve the reliability of voltage switch circuits and the operation of transformer substations.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2008年第20期69-71,74,共4页 Power System Protection and Control
关键词 电压切换 PT并列 反充电 母线失压 switch of voltage PT juxtaposition anti-inverse charge of voltage bus voltage failure
  • 相关文献

参考文献2

二级参考文献5

  • 1陈德树.继电保护原理[M].北京:中国电力出版社,1989..
  • 2国家电力调度通信中心.电力系统继电保护实用技术问答[Z].北京:中国电力出版社,1997..
  • 3DL/T5136—2001.火力发电厂、变电所二次接线设计技术规程[S].[S].,..
  • 4卓乐友.电力工程电气设计手册[M].北京:中国电力出版社,1989.
  • 5杜景远,崔艳.浅议PT断线、系统接地、母线失压的判据[J].继电器,2002,30(1):60-61. 被引量:16