期刊文献+

高压电容器直流局部放电测试抗干扰设计 被引量:3

Anti-interference design for high voltage capacitor PD detection under DC
在线阅读 下载PDF
导出
摘要 在局部放电测试试验中,环境干扰对局部放电的检测和识别结果产生很大影响。为提高局部放电测试的抗干扰,本文分析了局部放电测试中干扰的来源和种类,从试验电源、耦合电容、检测阻抗、保护电阻的选型到导线的连接,并采取隔离变压、滤波、接独立地等抗干扰设计改进测试系统。经试验,减小了环境中各种干扰,通过放电量、放电次数的对比试验得出Q-N图,也表明抗干扰设计后环境抗干扰有明显改善。 In the Partial Discharge (PD) testing, the interference will affect the results of PD test and identification. The sort and source of interference are introduced and analyzed during PD test. We consider the test power, coupling capacitor, test impedance, safe resistance and lead connect, and we add the transformer, filter,isolated ground etc. in anti-interference design. The interferences become smaller by experiment, and Q-N graph is gotten from contrastive experimentation of discharge magnitude and time, which indicates that the antiinterference has significant improvement.
作者 刘华昌
出处 《电测与仪表》 北大核心 2008年第7期41-43,共3页 Electrical Measurement & Instrumentation
关键词 局部放电 干扰 电容器 阻抗 PD, interference, anti-interference, capacitor
  • 相关文献

参考文献4

二级参考文献14

  • 1[1]IEC 60270.Partial Discharge Measurement[S].1996.
  • 2[2]M.Hoof,B.Freisleben and R.Patsch.PD Source Identification with Novel Discharge Parameters Using Counterpropagation Neural Networks[J].IEEE Trans.on Dielectrics and Electrical Insulation,1997,4(1):17-32.
  • 3[3]A.Krivda,E.Gulski,L.Satish,W.S.Zaengl. The Use of Fractal Features for Recognition of 3-D Discharge Patterns[J]. IEEE Trans.on Dielectrics and Electrical Insulation,1995,Vo1.2,No.5:889-892.
  • 4[4]T.Brosche,W.hiller,E.Fauser,W.Pfeiffer.Novel Characterization of PD Signals by Real-time Measurement of Pulse Parameters[J].IEEE Trans.on Dielectrics and Electrical Insulation,1999,6(1):51-59.
  • 5[5]M.Pompili,C.Mazzetti.Simultaneous Ultrawide and Narrowband Detection of PD Pulses in Dielectric Liquids[J].IEEE Trans.on Dielectrics and Electrical Insulation,1998,5(3):402-407.
  • 6[6]H.Borsi,et al.Seperation of Partial Discharges from Pulse-shaped Noise Signals with the Help of Neutral Networks[J]. IEE Proc.-Sci.Meas.Technol,1995,142(1):69-74.
  • 7[7]V.Nagesh,B.I.Gururaj.Automatic Detection and Elimination of Periodic Pulse Shaped Interferences in Partial Discharge Measurement[J].IEE Proc.-Sci.Meas.Technol,1994,141(5):335-342.
  • 8[2]Sher Zaman Khan, Zhu Deheng, Jin Xianhe et al. A new adaptive technique for on-line partial discharge monitoring[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1995, 5(6): 700~707
  • 9[3]Borsi H, Gockenbach E, Schichler U. Partial discharge(PD) measurements under noisy condition-possibilities and limits of digital noise rejection[A]. 8th ISH[C], 1993, 60(05): 17~20
  • 10[4]Kopf U, Feser K. Rejection of narrow-band noise and repetitive pulses in on-site PD measurements[J]. IEEE Trans on Dielectrics and Electrical Insulation, 1995, 2(6):1180~1191