摘要
介绍了全新风风管送风式空调(热泵)机组性能试验室气流组织的CFD数值模拟和机组性能试验情况。分析了被测室内外机放在一个试验环境间的气流组织和室外机对室内机的干扰问题。提出了全新风风管送风式空调(热泵)机组性能试验室的要求以及被试机室内外机的安装要求。
A numerical study on air distribution in the performance test room of complete fresh air ducted air-conditioning ( heat pump) units with the approach of CFD, an according experimental study and performance experiments in test room have been introduced. Air-distribution in an environment lab with indoor and outdoor units to be tested, together with interference of the outdoor unit to the indoor unit, has been analyzed. Consequently requests on the performance test room of complete fresh air ducted air-conditioning (heat pump) unit and installation requirements on indoor and outdoor units to be tested have been put forward.
出处
《流体机械》
CSCD
北大核心
2008年第5期58-62,共5页
Fluid Machinery
关键词
全新风机组
性能试验室
CFD
complete fresh air unit
performance test room
CFD