期刊文献+

变压器局部放电超高频检测影响因素分析 被引量:6

Factors of Influence on Partial Discharge Ultra-high Frequency Detection in Transformer
在线阅读 下载PDF
导出
摘要 采用仿真分析与试验研究相结合的方法,探索安装位置、变压器油和球形放油阀对超高频天线传感器驻波特性和检测能力的影响。分析表明,不同安装位置天线的谐振频率会有一定差异,但对检测到的信号幅值影响不大;变压器油使天线的谐振频率有所降低,改变了天线的驻波特性,但不影响天线的检测能力;将天线安装在球形放油阀入口处会严重影响单极子类天线的驻波特性,导致天线接收信号能力下降。 Simulation technique and experimental analysis are used to study the following factors: detection position, mineral oil and sphere oil drain valve, which affect the voltage standing-ware radio (VSWR) and detection performance of antenna sensor. The results and analysis procedures show that the antenna sensor fixed different detection positions have different resonance frequency, but signal amplitudes vary weekly. Furthermore, mineral oil can reduce resonance frequency and change VSWR, but weekly affect detection performance of antenna sensor. It is also suggested that installed the antenna in the sphere oil drain valve entrance can heavily affect VSWR of monopole antenna and reduce detection performance, so some new technique should be used to handle the problem.
出处 《重庆大学学报(自然科学版)》 EI CAS CSCD 北大核心 2008年第2期150-154,共5页 Journal of Chongqing University
基金 重庆市自然科学基金重点资助项目(2006BA3018)
关键词 变压器 局部放电 超高频 谐振频率 驻波特性 transformer partial discharge ultra-high frequency resonance frequency voltage standing-ware radio
  • 相关文献

参考文献11

  • 1JUDD M D, LI YANG, HUNTER IAN B B, Partial discharge monitoring for power transformers using UHF sensors part 1 : sensors and signal interpretation [ J ]. IEEE Electrical Insulation Magazine, 2005 ,21 ( 2 ) :5-14.
  • 2JUDD M D, LI YANG, HUNTER IAN B B. Partial discharge monitoring for power transformers using UHF sensors part 2 : field experience [ J ]. IEEE Electrical Insulation Magazine, 2005 ,21(3) :5-13.
  • 3RAJA K, DEVAUX F, LELAIDIER S. Recognition of discharge sources using UHF PD signatures[J] . IEEE Electrical Insulation Magazine,2002,18 (5) :8-14.
  • 4唐志国,李成榕,黄兴泉,王伟,程序,李君.基于辐射电磁波检测的电力变压器局部放电定位研究[J].中国电机工程学报,2006,26(3):96-101. 被引量:51
  • 5CLEARY G P,JUDD M D. UHF and current pulse measurements of partial discharge activity in mineral oil [ J ]. lEE Proc-Sei Technol,2006,153 ( 2 ) :47-54.
  • 6ASCHENBRENNER D, KRANZ H-G, RUTGERS W R, et al. On line PD measurements and diagnosis on power transformer [ J ]. IEEE Transactions on Dielectrics and Electrical Insulation,2005,12(2) :216-221.
  • 7孟延辉,唐炬,许中荣,张晓星,胡晶晶.变压器局部放电超高频信号传播特性仿真分析[J].重庆大学学报(自然科学版),2007,30(5):70-74. 被引量:13
  • 8RAMIREZ C, MOORE P J. The effect of electrical connection structures on the spectra of radiated partial discharge signals[ C]//Annual Report Conference on Electrical Insulation and Dielectric Phenomena, New York : IEEE, 2005 : 397-400.
  • 9王伟,唐志国,李成榕,黄兴泉,李信,王伟.用UHF法检测电力变压器局部放电的研究[J].高电压技术,2003,29(10):32-34. 被引量:34
  • 10SELLARS A G, MACGREGOR S J, FARISH O. Calibrating the UHF technique of partial discharge detection using a PD simulator[ J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1995, 2 ( 1 ) :46-53.