期刊文献+

基于桥式逆变器中性线谐波电流治理装置研究 被引量:4

Study on a Novel Active Filter to Cancel the Neutral Harmonic Current based on Bridge Inverter
在线阅读 下载PDF
导出
摘要 介绍了低压供电系统中一种新型低电压应力的中性线谐波治理装置,研究了该装置的主电路结构并对其工作原理进行了分析,同时对装置的谐波电流检测方法、控制策略等问题进行了研究,给出了该有源电力滤波器(APF)的主电路结构图,提出了基于自适应干扰对消原理的谐波电流自适应检测方法,补偿策略主要采用重复学习Boost控制方法。在实际工程中采用DSP+FPGA为控制核心。试验结果表明,该装置具有电压应力低、结构和控制简单、运行可靠等优点。 This paper introduces a novel low-voltage equipment to cancel the neutral harmonic current, researchs the main circuit of this equipment,and analyzes the equipment working theory,then studies the method to detect the harmonic current and gives the control scheme.The Active Power Filter (APF) main circuit is given.The adaptive method based on adaptive disturbance elimination principle is proposed.The method for compensation control is done by integrated learning Boost mode which is full described.Considering practical project the main control CPU is DSP and FPGA.The experimental result shows this equipment have higher stability, simple main circuit and control method, and higher reliability.
出处 《电力电子技术》 CSCD 北大核心 2007年第11期12-14,17,共4页 Power Electronics
关键词 逆变器 滤波器 谐波/自适应谐波检测 重复学习控制 inverter filter harmonic / adaptive harmonic detection integrated learning boost mode
  • 相关文献

参考文献5

二级参考文献19

  • 1Aredes M, Hafner J, Heumann K. Three-phase Four-wire Shunt Active Filter Control Strategies. IEEE Trans on Power Electronics, 1997, 12 (2): 311-318.
  • 2Quinn C A, Mohan N, Mehta H. A Four-wire Currentcontrolled Converter Provides Harmonic Neutralization in Threephase Four-wire Systems. In:APEC' 1993. California: 1993.841 - 846.
  • 3Peng F Z, Adams D J. Harmonic Sources and Filtering Approaches-Series/Parallel, Active/Passive, and Their Combined Power Filters. In:IEEE IAS'99. Arizona:1999. 1~8
  • 4Quinn C A, Mohan N, Mehta H. A Four-wire, Current-controlled Converter Provides Harmonic Neutralization in Three-phase, Four-wire Systems. In:APEC' 1993. California:1993. 841~846
  • 5Aredes M, Hafner J, Heumann K. Three-phase Four-wire Shunt Active Filter Control Strategies. IEEE Trans on Power Electronics, 1997, 12(2):311~318
  • 6Kamath G, Ohan N. A Novel Reduced Rating Active Filter for 3-phase, 4-wire Loads. In:IAS' 1994. Colorado:1994. 936~940
  • 7Enjeti P N, Shireen W, Packebush P, et al. Analysis and Design of a New Active Power Filter to Cancel Neutral Current Harmonics in Three-phase Four-wire Electric Distribution Systems. IEEE Trans on Industry Applications, 1994, 30(6):1565~1572
  • 8Basic D, Ramsden V S, Muttik P K. Hamonic filtering of high-power 12-pulse rectifier loads with a selective hybrid filter system. IEEE Trans. Industrial Electronics,2001,48 (6): 1118-1127
  • 9Cheng P T, Bhattacharya S, Divan D M. Application of dominant harmonic active filter system with 12 pulse nonlinear loads. IEEE Trans. Power Delivery.1999,14(2): 642-647
  • 10Fujita H, Yamasaki T, Akagi H. A hybrid active filter for damping of harmonic resonance in industrial power systems. IEEE Trans. on Power Electronics, 2000, 15(2) : 215-222

共引文献50