以实际液体除湿空调系统为对象,改变液体除湿空调系统中除湿器、再生器的输入空气、溶液的温度、湿度、流量、浓度等参数,研究输入参数变化对输出参数的影响.在优化的系统运行参数条件下,改变供能热源温度,研究液体除湿空调系统整体运行时输出参数的变化和系统制冷量、耗能量及COP值的变化规律.实验结果表明,当再生热源为90℃时,空调送风温度稳定在21℃,热力系数为0.6左右,基本能满足舒适性空调的送风要求.
Based on the experimental research on the liquid desiccant air-conditioning system, the feasibility and economical efficiency of the system are studied when the parameters of temperature, humidity, flow amount, consistence etc. of the air and solution input into the dehumidifier and regenerator are changed. The results show that when the temperature of the re-generation is 90℃, the thermodynamic coefficient of the system is about 0.6, the supply air temperature of the air-conditioning system remains stable at 21 ℃, so that the air-conditioning system can meet the comfortable need of people.