期刊文献+

750kV扩径导线的运行情况总结 被引量:14

Operation Summary of the 750 kV Oversized Conductor
原文传递
导出
摘要 我国750kV输变电示范工程线路全长140.705km,其中使用了24.462km的扩径导线。输电线路使用扩径导线,直接投资有所降低,但运行中损耗增加。如果750kV线路载流较小,可以考虑使用扩径导线,较大时不宜采用扩径导线。展放扩径导线时发生了跳股现象,发生跳股的原因是导线通过滑轮时发生跳股的股线受到了两侧导线的挤压。经过1年多的运行,扩径导线没有发生明显变化。 The total length of the nation's 750 kV power transmission demonstration line is 140.705 km, among them, 24.462 km using oversized conductor. The application of oversized conductor reduces cost, but increases operating loss. Only when the carrying current of the 750 kV line is low enough, can oversized conductor be considered. Otherwise, it should not he used. The cause of strand jump during stringing is that the jumped strand that s is squeezed by conductors on both sides when conductor goes through the pulley. After more than one year's operation, there is hardly any change in the oversized conductor.
机构地区 西北电网公司
出处 《电力建设》 2007年第10期43-46,共4页 Electric Power Construction
关键词 750kV 线路 扩径导线 跳股 经济分析 运行总结 750 kV line oversized conductor strand jump economic analysis operation summary
  • 相关文献

参考文献9

  • 1西北电力设计院.750kV官亭-兰州东送电线路工程总说明书
  • 2国家电网公司.750 kV输变电示范工程建设总结(试验调试分册).北京:中国电力出版社,2006
  • 3国家电网公司.750 kV输变电示范工程建设总结(施工分册).北京:中国电力出版社,2006
  • 4《110-500 kV架空送电线路设计技术规程》(DL/T 5092-1999)
  • 5《750 kV架空送电线路设计暂行技术规定》(Q/GDW102-2003)
  • 6国家电网公司.750 kV输变电示范工程建设总结(科研分册).北京:中国电力出版社,2006
  • 7田子恒.750kV输电线路示范工程扩径导线展放质量分析[J].超高压送变电动态报道,2005,(6):1-4.
  • 8《750kV架空送电线路LGJK-300/50扩径导线架线施工工艺导则》(Q/GDW124-2005)
  • 9毕庶达.750 kV输电线路扩径导线跳股原因的分析[J].电力建设,2006,27(9):1-3. 被引量:12