摘要 基于不可压缩黏性流体N-S方程和K-ε两方程湍流模型,采用有限容积法对某工程变制冷剂流量空调室外机周围流场进行了数值计算,得到了室外机周围的气流速度和温度分布及室外机的进风温度,分析了多层建筑中室外机安放条件对空调系统性能的影响。结果表明,变制冷剂流量空调室外机进、排风口不宜同侧布置,如果因建筑条件限制只能同侧布置时,同一设备阳台上室外机数量应少于4台。根据研究结果及实际建筑条件改进和优化了空调室外机安放设计。 Based on the N-S equation of the incompressible viscous fluid and K-ε turbulent model, simulates the air distribution around outside units using the finite volume method, obtains the distribution of temperature and velocity around outside units and the inlet temperature of outside units, and analyses the effects of outside unit placement on the performances. As a result, it is unsuitable to place the inlet and outlet of outside units on the same side of a balcony, and if necessary because of the building structure restriction, there should be less than 4 units on one balcony. Optimizes the original placement of outside units according to the simulation results and actual building structure.
出处 《暖通空调》 北大核心 2007年第5期97-100,共4页 Heating Ventilating & Air Conditioning
关键词 变制冷剂流量空调系统 室外机 性能 数值计算 variable refrigerant volume air conditioning system, outside unit, performance, numerical calculation
  • 相关文献

参考文献3

  • 1毛红梅,毕海权.司机室气流组织数值计算研究[J].铁道车辆,2005,43(10):19-21. 被引量:2
  • 2Versteeg H K,Malasekera W.An introduction to computational fluid dynamics[M].北京:世界图书出版社,2000.
  • 3MITSUBISHI ELECTRIC数据手册--变频多联分离式空调机,2002.

二级参考文献1

  • 1VersteegH.K Malalasekera W.An introduction to computational fluid dynamics[M].北京,世界图书出版公司,2000..

共引文献1

同被引文献54

引证文献9

二级引证文献23

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部