摘要
采用实验室研究方法研究了侧送风与散流器送风两种送风方式对人体热舒适的影响,统计结果表明:侧送风与散流器送风下的中性温度分别为28.64℃和25.96℃,不满意率分别为4.34%和6.82%,根据热感觉投票值得出了两种送风方式下80%,90%满意率的温度范围,并与ASHRAE Standard 55-1992中夏季舒适区的温度进行了对比。
The experiment was done in laboratory conditions to research the effect of two kinds of different air supply pattens on thermal comfort, The result showed that the neutral temperature under lateral supply patten and rectangle diffuser patten are 28.64℃and 25.96℃ respectively, the percentage of dissatisfied are 4.34 % and 6.82 % respectively. Got the temperature scope of 80 % and 90 % satisfaction by thermal sensation and compared with ASHRAE 55-1992.
出处
《山西建筑》
2007年第19期5-6,共2页
Shanxi Architecture
关键词
热舒适
热感觉
调查问卷
送风方式
操作温度
thermal comfort, thermal sensation, questionnaire, air supply system, operative temperature