期刊文献+

三相四线统一电能质量调节器的控制策略 被引量:4

A Control Strategy for Three-phase Four-wire Unified Power Quality Conditioner
在线阅读 下载PDF
导出
摘要 针对电网输入电压的不平衡、非正弦及负载的不平衡、非线性特性,提出了一种基于三相静止坐标系下的三相四线统一电能质量调节器(UPQC)的协调控制策略。该策略将UPQC的串联变流器控制为基波正弦电流源,而并联变流器控制为基波正弦电压源,从而实现了三相四线UPQC对电能质量的综合控制能力,既改善了电网侧的电能质量问题,实现了电网输入电流的正弦及单位输入功率因数,也改善了负载侧的电能质量问题,实现了负载电压的平衡、额定及正弦。10kVA系统实验装置的实验结果表明了该控制策略的有效性。 In order to govern unbalancing and distorting voltages in network and suppress the influences of nonlinear loads, a coordinated control strategy based on ABC rest frame for three-phase four-wire unified power quality conditioner (UPQC) is introduced. By controlling the series converter as a fundamental sine current source and the parallel converter as a fundamental sine voltage source, the proposed control strategy can make the UPQC carries out all of the control terms: the sinusoidal input current, the unit input power factor, the sinusoidal and balanced output voltage with normal value to improve power qualities at the side of network's and at the side of loads. The experimental results of 10 kVA prototype verify that the strategy is feasible.
出处 《电力系统自动化》 EI CSCD 北大核心 2007年第8期56-60,共5页 Automation of Electric Power Systems
关键词 统一电能质量调节器(UPOC) 串联变流器 并联变流器 正弦电压源 正弦电流源 协调控制 unified power quality conditioner (UPQC) series converter parallel converter sinusoidal voltage-source sinusoidal current-source coordinated control
  • 相关文献

参考文献10

二级参考文献27

  • 1朱鹏程,李勋,康勇,陈坚.统一电能质量控制器控制策略研究[J].中国电机工程学报,2004,24(8):67-73. 被引量:112
  • 2张秀娟,姜齐荣,韩英铎.一种新型的单相统一电能质量调节器[J].电力系统自动化,2004,28(23):76-80. 被引量:18
  • 3王晓钰,刘进军,何益宏,黄立明,王兆安.用于通用电能质量控制器的一种简单补偿策略和统一控制方法[J].电工技术学报,2004,19(12):47-52. 被引量:6
  • 4Jeon Seong-Jeub, Cho Gyuhyeong. A series-parallel compensated uninterruptible power supply with sinusoidal input current and sinusoidal output voltage[A]. IEEE PESC[C]. 1997: 297-303.
  • 5Rathmann S, Warner HA. New generation UPS technology, the delta conversion principle[A]. IEEEIAS[C]. 1996: 2389-2395.
  • 6Farrukh, Kamran, Thomas, Habetler G. A novel on-line UPS with universal filtering capabilties[J]. IEEE Trans. on Power Elec.1998,13(3): 410-418.
  • 7Silva S A O, Donoso-Garcia P, Cortizo P C A, et al. Comparative analysis of control algorithms for three-phase line-interactive UPS system with series-parallel active power-line condition using SRF method[A]. IEEE/PEDS[C]. 2000: 1023-1028.
  • 8RenzBA, KeriA, MehrabanAS, etal. AEPunifiedpowerfiow controller performance. IEEE Trans. Power Delivery, 1999, 14(9):1374-1381.
  • 9Graovac D, Katic V, Rufer A. Power quality compensation using universal power quality conditioning system[J]. Power Engineering Review, IEEE, 2000, 20(12): 58-60.
  • 10Hideaki Fujita, Hirofurni Akagi. The unified power quality conditioner:the integration of series- and shunt-active filters[J]. IEEE Trans. Power Electronics, 1998, 13(3): 315-322.