期刊文献+

热管式空调机组在空调系统的节能应用研究 被引量:14

Study on energy saving in air-conditioning system using heat pipe air-conditioner
在线阅读 下载PDF
导出
摘要 以广州地区的办公建筑为例,就一次回风集中空调系统在空气处理过程中采用热管式空调机组时.不同室内设计温度下的空调系统能耗进行了分析,并且与常规的一次回风集中空调系统的耗能量进行了比较.研究结果表明:在相同的室内设计温度下,采用热管式空调机组处理空气的一次回风集中空调系统比常规的一次回风集中空调系统节省冷量和再热量.节能效果随着室内设计温度的提高而提高.在通常的室内设计温度22.26℃范围内,相应的冷量节能率为24.3%-25.8%,总耗能量的节能率为39.1%-41.0%. Taking an office building in Guangzhou as an example, this paper investigated the energy consumption of a central air-conditioning system with primary return air using heat pipe air-conditioner at different indoor design temperatures. The study shows that compared with the energy consumption of conventional central air- conditioning system with primary return air, the heat pipe air-conditioning system can save cooling and reheating energy. The capacity of saving energy increases along with the increase of indoor design temperature. In the range of 22- 26℃ of indoor design temperature, the rate of energy saving is 24.3% - 25.8% for cooling energy consumption and 39.1% -41.0% for total energy consumption, which shows a remarkable energy saving capability.
出处 《广州大学学报(自然科学版)》 CAS 2006年第6期81-85,共5页 Journal of Guangzhou University:Natural Science Edition
基金 广州市建设基金项目(2006)
关键词 热管式空调机组 节能率 一次回风集中空调系统 heat pipe air-conditioner rate of energy saving central air-conditioning system with primary return air
  • 相关文献

参考文献1

共引文献1

同被引文献87

引证文献14

二级引证文献43

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部