摘要 就干工况风机盘管加独立新风空调系统的末端风机盘管的冷水进水温度的确定方法进行探讨,并得出干工况下风机盘管临界进水温度的计算公式,而临界进水温度随着室内空气露点温度的提高而提高。在实际应用中,干式盘管的实际进水温度应高于临界进水温度,但低于室内空气的露点温度。 Makes a discussion for the determination method of inlet water temperature of fan-coil unit in dry cooling condition with fresh air system, gives the formula to calculate critical inlet water temperature in dry cooling condition of fan-coil unit, and it's changed with dew - point temperature of indoor air. In practical application,inlet water temperature should be higher than critical inlet water temperature and be lower than dew-point temoerature of indoor air.
作者 倪美琴
机构地区 扬州大学
出处 《制冷与空调》 2006年第6期83-85,共3页 Refrigeration and Air-Conditioning
关键词 风机盘管 干工况 临界进水温度 露点温度 fan-coil unit dry cooling conditio critical inlet water temperature dew-point temperature