期刊文献+

高压二氧化碳节流排放堵塞实验 被引量:6

Experimental Study of Blockage during Throttling Release of CO_2 under High Pressure
在线阅读 下载PDF
导出
摘要 采用透明玻璃管构造了匹配各种运行情况下安全阀内流道的结构,观测了阀前CO2状态对固体CO2形成和堵塞位置的影响;采用针阀代替安全阀,实验研究了安全阀进口干度、阀开度对安全阀及下游管路中流动堵塞的影响.实验表明:排放蒸气和排放液体同样容易发生堵塞和冻结现象,只是前者在阀内,而后者在阀后管道中;阀开度小时堵塞在阀内,开度大时堵塞在阀后管道中.为了保证安全阀的正常有效运行,建议安全阀出口的管路直径不宜太大,而且应避免向上排放和截面的多次突变.当排放CO2蒸气时应安装消除静电的设施. The possible formation and blockage of the solid phase is unique for CO2 safety valves. To experimentally investigate it, needle valves and transparent glass tubes with flow channels similar to that of safety valves were used instead of the safety valve. The flow in the glass tube was observed, and the influence of the vapor quality of releasing fluid and the opening of the valve was experimentally investigated. According to the experimental results, both release of vapor and liquid COz can cause blockage and freezing, but the former is in the safety valve, while the latter in the downstream pipeline. In order to guarantee the normal and effective operation of C02 safety valve, it is recommended that the outlet pipeline should not have a too large diameter, and upward flow and twice enlargements of cross section should be avoided. Because of high back pressure, back pressure balanced safety valves are recommended. When vapor is released, device to discharge the stationary electricity is needed.
出处 《上海交通大学学报》 EI CAS CSCD 北大核心 2006年第8期1417-1421,共5页 Journal of Shanghai Jiaotong University
关键词 二氧化碳 安全阀 堵塞 开度 干度 carbon dioxide (CO2) safety valve blockage opening vapor quality
  • 相关文献

参考文献7

  • 1Kim S G,Kim M S.Experiment and simulation on the performance of an autocascade refrigeration system using carbon dioxide as refrigerant[J].International Journal of Refrigeration,2002,25:1093-1101.
  • 2Girotto S,Minetto S,Neksa P.Commercial refrigeration system with CO2 as refrigerant experimental results[J].International Journal of Refrigeration,2004,27(7):717-723.
  • 3Barry.Supermarkets buy into CO2 refrigerant systems[J].Refrig Air Cond,2002,104:29-38.
  • 4Pearson A.Ammonia/CO2 refrigeration system breaks new ground[J].Refrig Air Cond,2002,104:23-25.
  • 5Krings F.CO2 safety valve[D].Koln:Koln University,1997.
  • 6Rozhentsev A V.A throttle-sublimation refrigerating machine using the solid coolant with changeable porous structure[C]//Proceedings of 19th International congress of refrigeration.Paris:International Institute of Refrigeration,1995:176-183.
  • 7BS EN 13136-2001,Refrigerating systems and heat pumps-Pressure relief devices and their associated piping-Methods for calculation[S].