期刊文献+

水喷淋对热烟气冷却效应的模拟计算 被引量:6

Numerical simulation on the cooling effect of water sprinkler on hot smoke
在线阅读 下载PDF
导出
摘要 分析了水喷淋液滴与热烟气传热传质的过程。采用场模拟方法对一系列假定的算例进行计算,探讨了水喷淋作用对热烟气的冷却效果。结果表明,水喷淋作用后烟气层的温度大大降低,烟气温度的变化受喷淋模式和喷头工作压力的影响。最后对水喷淋系统的设计给出了一些建议。 This paper is inclined to present the authors' numerical simulation on the heat and mass transfer of water sprinkler droplets over the hot smoke. For our purpose, we have studied some cases on water sprinkling and analyzed the its cooling effect on the hot smoke with CFD method. As is known, the cooling effect of water sprinkling is one of the most important applications for fire control. Therefore, we have chosen and studied different working pressures and different sprinkler spray models such as solid cone model and hollow cone models. As a result, it has been found that: 1 ) the temperature may decrease significantly after the water sprinkler is discharged; 2) due to the cooling effect and momentum effect of the water spray, the smoke layer is very likely to lose its stability; 3) the temperature of smoke is inversely affected by the working pressure and spray models of water sprinkling; 4) for the high ceiling clearance buildings, it is recommended to choose the sprinkler head type in accordance with the fire load in the building in order to reduce the possibility of "smoke logging".
出处 《安全与环境学报》 CAS CSCD 2006年第4期99-103,共5页 Journal of Safety and Environment
基金 国家重点基金项目(50536030)
关键词 安全工程 水喷淋 烟气 冷却效应 safety engineering water sprinkler smoke cooling effect
  • 相关文献

参考文献12

  • 1CHOW W K. Performance of sprinkler in atrium [J]. Journal of Fire Science, 1996, 14: 467-488.
  • 2MORGAN H P. Heat transfer from a buoyant smoke layer beneath a ceiling to a sprinkler spray [ J ]. Fire and Materials, 1979,3 ( 1 ) : 34-38.
  • 3CHOW W K, FONG N K. Numerical simulation on cooling of the fireinduced air flow by sprinkler water sprays [ J ]. Fire Safety Journal,1991, 17: 263-290.
  • 4BEYLER C L, COOPER L Y. Interaction of sprinklers with smoke and heat vents [J]. Fire Technology, 2001, 37:9-35.
  • 5WONG S C, LIAO X X, YANG J R. A simplified theory of the ignition of single droplets under forced convention [J]. Combustion and Flame,1997, 110: 319-334.
  • 6CHOW W K, FONG N K. Numerical studies on the interaction of sprinklers and the hot layer [Jl. Architectural Science Review, 1993, 36:103-111.
  • 7HUA J S, KUMAR K, KHOO B C, et al. A numerical study of the interaction of water spray with a fire plume [ J]. Fire Safety Journal,2002, 37: 631-657.
  • 8MCGRATYAN K B, BAUM H R, REHM R G, et al. Fire dynamics simulator ( version 3) - technical reference guide, NISTIR 6783 [ R ].2002.
  • 9TANAKA F, OHMIYA Y, HAYASHI Y. Numerical simulation of a compartment fire in activation of a sprinkler [ C]//Proceedings of 6^th Asia-Oceania Symposium on Fire Science and Technology, Daegu, Korea, March, 2004 : 980-990.
  • 10NAM S. Actuation of sprinklers at high ceiling clearance facilities[J].Fire Safety Journal, 2004, 39 : 619-642.