期刊文献+

Correlations of Two-phase Friction of Refrigerant in Horizontal Smooth Tube with 2.5 mm inside Diameter

Correlations of Two-phase Friction of Refrigerant in Horizontal Smooth Tube with 2.5 mm inside Diameter
在线阅读 下载PDF
导出
摘要 Two-phase flow pressure drop measurements are made during phase change heat transfer process of R-22 in small horizontal smooth tubes with 2.5 mm inside diameter. Conclusions are drawn that the quality corresponding to pressure gradient peak value of small tubes became higher than that of large tubes and that effects of quality on pressure drop become weak as the increase of mass flux. The experiment data are compared with predicted values of the state-of-the-art correlations from the open literature, which indicates that most of the state-of-the-art correlations fail to predict the present experimental data. Chisholm model shows a relatively better predictive ability than the other empirical correlations because it has the lowest mean deviation of 26.7%. But the predicted values of Chisholm model are 50% lower than experimental data when quality becomes higher. In this regard, an new empirical correlation based on Chisholm model is developed and this modified Chisholm correlation can describe 95% of the present data with ±20% mean deviations. Two-phase flow pressure drop measurements are made during phase change heat transfer process of R-22 in small horizontal smooth tubes with 2. 5 mm inside diameter. Conclusions are drawn that the quality corresponding to pressure gradient peak value of small tubes became higher than that of large tubes and that effects of quality on pressure drop become weak as the increase of mass flux. The experiment data are compared with predicted values of the state-of-the-art correlations from the open literature, which indicates that most of the state-of-the-art correlations fail to predict the present experimental data. Chisholm model shows a relatively better predictive ability than the other empirical correlations because it has the lowest mean deviation of 26.7%. But the predicted values of Chisholm model are 50% lower than experimental data when quality becomes higher. In this regard, an new empirical correlation based on Chisholm model is developed and this modified Chisholm correlation can describe 95% of the present data with ±20% mean deviations.
出处 《Journal of Donghua University(English Edition)》 EI CAS 2006年第1期78-83,共6页 东华大学学报(英文版)
关键词 REFRIGERANT flow boiling pressure drop performance small tube 制冷剂 流动沸腾 摩擦 管材
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部