摘要 提出山区大跨越段的220 kV定型双回直线塔塔头尺寸应优化设计,将V形串应用到双回直线塔(最大使用档距650 m)的上导线,塔头处避雷线对上导线的保护角可减少9.88,°档距中央避雷线对上导线的保护角可减少13.3,°从而有效降低绕击率。V形串单支复合绝缘子可比常规长300 mm,根据不平衡绝缘原理减少线路型氧化锌避雷器的安装数量。 Puts forward that 220 kV double circuit tangent tower must be optimum designed on big across of mountainous region, the "V" string being installed upper conductor on double circuit tangent tower (max span is 650 m), the upper conductor protected angle may reduce 9.88°on tower, and reduce 13.3°between span center. The length of composite insulator on "V" string may be more 300 mm than common composite insulator, therefore reduce back strike probability of upper conductor; according to unbalanced insulation principle, may reduce the installed amount of line surge arrester,
出处 《中国电力》 CSCD 北大核心 2006年第4期29-33,共5页 Electric Power
关键词 大跨越段 220kV 双回双分裂直线塔 V形串 设计优化 big across 220 kV double circuit tangent tower "V" string optimum design
  • 相关文献

参考文献9

二级参考文献17

  • 1刘有为,杜澍春,马晋华,李明贵,顾南峰.高压交流线路用金属氧化物避雷器[J].电力设备,2000,1(2):1-8. 被引量:11
  • 2罗真海.110kV、220kV架空送电线路复合绝缘子并联间隙防雷保护研究.中国电力科学研究院硕士研究生论文[M].,2000,6..
  • 3-.输电线路防雷新技术研讨会资料[M].中国电力科学研究院,2000,4..
  • 4[10]CIGRE WG 22.03. Worldwide service experience with HV composite insulators[J]. Electra, 2000(191): 27-43.
  • 5Matsumoto Y, Sakuma O. Measurement of lightning surges on test transmission line equipped with arresters struck by natural and triggered lightning[J]. IEEE Transactions on Power Delivery, 1996, 11 (2): 996~1002.
  • 6Yamada Takeshi, Sawada Jun. Development of suspension-type arresters for transmission lines[J]. IEEE Transactions on Power Delivery, 1993, 8(3): 1052~1053.
  • 7Guan Z, Zhang R. Calculation of DC and AC flashover voltage of polluted insulators [J]. IEEE Trans on Electrical Insulation, 1990,25(4): 723-729.
  • 8Rizk F A M, Rezazada A Q. Modeling of altitude effects on AC flashover of polluted high voltage insulators [J]. IEEE Trans on Power Delivery, 1997, 12(2): 810-822.
  • 9Jaafar S, Ahmad A S, Ghosh P S. A new approach in modeling AC flashover voltage for polluted insulator [C]. 2002 Annual Report Conference on Electrical Insulation and Dielectric Phenomena,Cancun, Mexico, 2002: 558-561.
  • 10GB/T4585.2-91.交流系统用高压绝缘子人工污秽试验方法-固体层法[S].[S].,..