根据3/2断路器接线方式的特点,结合500kV敬亭变电站的验收、运行经验和工程实际,提出了3/2断路器接线方式下重合闸与保护的配合问题及改进措施,进而优化运行操作,提高系统的运行稳定性及可靠性。
According to the performance of 3/2 connections and the acceptance test and operation experience and practice of the 500 kV substation, this paper puts forward the protection mate and improvements of the breaker reclose under 3/2 connections to optimize operations and heighten the stability and reliability of the power system.
出处
《安徽电力》
2006年第1期26-28,40,共4页
Anhui Electric Power