期刊文献+

PP-R管水锤波速实验研究 被引量:8

Experimental Study of the Wavespeed of Water Hammer in PP-R Pipe
在线阅读 下载PDF
导出
摘要 通过实验测定了S3.2,dn90×en12.3mm规格PP—R管路系统的水锤波速值为390~450m/s,平均波速为425.25m/s。按厚壁管水锤波速计算公式得到的结果为321.33m/s,该值比实测值小24%。因此,计算PP-R管水锤波速的公式有待进一步研究。 Based on field tests, the measured wavespeed of water hammer in PP-R pipe in type S3.2,dn90×en12.3 mm polypropylene(PP-R) pipe is between 390 m/s and 450 m/s , and average value is 425.25 m/s. While result calculated by present wavespeed formula of thick pipe is only 321.33 m/s, which is 24% less than the test result. Accordingly the formula calculating the wavespeed of water hammer of PP-R pipe needs to be further studied.
出处 《西安理工大学学报》 CAS 2006年第1期46-48,共3页 Journal of Xi'an University of Technology
基金 国家自然科学基金资助项目(50279041) 陕西省重点实验室科研计划项目(05JS35)
关键词 PP—R管 水锤波速 实验 PP-R pipe wavespeed of water hammers experiment
  • 相关文献

参考文献3

  • 1沙国定.误差分析与测量不确定度评定[M].北京:中国计量出版社,2003.
  • 2怀利E B,斯特里特V L.瞬变流(Fluid Transients)[M].清华大学流体传动与控制教研组译.北京:水利电力出版社,1983.
  • 3Robert LSanks.Pumping Station Design[M].2nd ed.Boston:Butterworth-Heinemann,1998.