由于断路器并口电容引起的铁磁谐振研究 被引量:2

Study on Ferroresonance Caused by Breaker Parallel Capacitance
在线阅读 下载PDF
导出
摘要 根据北京某220 kV变电站曾发生的铁磁谐振现象,利用电磁暂态软件分析了该变电站220 kV母线上接有电磁式电压互感器时,由于互感器和断路器并口电容组成了谐振回路,从而导致的铁磁谐振发生的概率。并且根据消除谐振回路的抑制铁磁谐振的思路,将母线上的电磁式电压互感器全部更换为电容式电压互感器后在电磁暂态软件下模拟。结果表明,对上述两种情况分别进行500次分断路器操作,带有电磁式电压互感器时发生谐振的可能性很大,而换成电容式电压互感器后发生谐振的可能性几乎为零。因此,用电容式电压互感器代替电磁式电压互感器从根本上消除了铁磁谐振回路,是一种效果很好的铁磁谐振抑制措施。 According to a ferroresonance accident occurred at one 220 kV station in Beijing, Authors use electromagnetic transient simulation software to simulate the probability of ferroresonanee occurrence when inductive voltage transformer connected to the station's 220 kV bus line and breaker parallel capacitance form a resonance circuit. According to some ferroresonance restraining measures, the inductive voltage transformers are replaced with capacitive voltage transformers. Finishing 500 switch operations ,some results are obtained. When bus was connected with inductive voltage transformer, there is high possibility to occur ferroresonancc when doing switch operations. While using capacitive voltage transformer,there is no such possibility. Therefore,to replece inductive voltage transformer with capacitive voltage transformer is a good measure to restrain ferroresonance.
出处 《华北电力技术》 CAS 2006年第3期7-10,共4页 North China Electric Power
关键词 中性点接地系统 铁磁谐振 电压互感器 抑制措施 断路器并口电容 neutral-grounded system ferroresonance voltage transformer restraining measure breaker parallel capacitance
  • 相关文献

参考文献2

  • 1M R Iravani. A K S Chaudhary and W J Giesbrecht,et al. Modeling and Analysis Guidelines for Slow Transients- Part Ⅲ :The Study of Ferroresonance[J]. IEEE Transactions on Power Delivery , 2000,15 (1): 255- 265
  • 2李红斌,刘延冰,叶国雄,王晓琪.电容式电压互感器铁磁谐振的数值仿真[J].高压电器,2004,40(2):124-125. 被引量:31

二级参考文献2

共引文献30

同被引文献33

引证文献2

二级引证文献26

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部