供应室万级空气净化的效果观察 被引量:7

The effect of air purification on 10,000 degree clean room in supply rooms
全文增补中
导出
摘要 介绍了该院在供应室的主要操作间安装了净化设备,并对其中包装间进行了实验检测。在静态下,开机净化后,室内空气湿度及细菌数量明显低于未开机净化前(P<0.01)。在动态情况下,检测了万级洁净室的主要技术指标,结果均达到了国家规定标准。 This article introduced that purifying equipments were installed in the major operating departments of supply rooms in hospital, and that experimental tests were done on the packing department. In statil state, the air humidity and the number of bacteria in the room after purification was obviously lower than that before purification (P<0. 01). In trending conditions, the main technical index on 10 ,000 degree clean rooms were examined, all of the results were up to the national standards.
出处 《中华护理杂志》 CSCD 北大核心 1996年第2期68-69,共2页 Chinese Journal of Nursing
关键词 供应室 空气净化 洁净室 Air purification Clean room Supply room