摘要
对比我国和美国、英国混凝土保护层设计和施工标准,量测3栋建筑混凝土柱的保护层厚度;说明我国混凝土结构设计保护层偏薄,而施工标准要求过高;提出改进混凝土结构保护层设计与施工的建议.
The design and construction criteria of concrete cover specified by China, American and Britain were compared. The column cover thickness of three buildings were measured. It is indicated that domestic design concrete cover is too thin and the construction requitment is too high. Suggestions for modifying design and construction of concrete cover are put forward.
出处
《建筑技术开发》
2005年第12期86-87,共2页
Building Technology Development