期刊文献+

On-Line Partial Discharge Monitoring and Diagnostic System for Power Transformer 被引量:3

On-Line Partial Discharge Monitoring and Diagnostic System for Power Transformer
原文传递
导出
摘要 This paper introduces a computerized on-line partial discharge (PD) monitoring and diagnostic system for transformers. The system, which is already in use in a power station, uses wide-band active transducers and a data acquisition unit with modularized and exchangeable components. The system software is a power equipment monitoring and diagnostic system, which is based on the component object model, and was developed for monitoring multiple parameters in multiple power supply systems. The statistical characteristics of PDs in power transformers were studied using 7 experimental models for simulating PDs in transformers and 3 models for simulating interfering discharges in air. The discharge features were analyzed using a 3-D pattern chart with a three-layer back-propagation artificial neural network used to recognize the patterns. The results show that PDs in air and oil can be distinguished. The model can be used for interference rejection on-line monitoring of partial discharge in transformers. This paper introduces a computerized on-line partial discharge (PD) monitoring and diagnostic system for transformers. The system, which is already in use in a power station, uses wide-band active transducers and a data acquisition unit with modularized and exchangeable components. The system software is a power equipment monitoring and diagnostic system, which is based on the component object model, and was developed for monitoring multiple parameters in multiple power supply systems. The statistical characteristics of PDs in power transformers were studied using 7 experimental models for simulating PDs in transformers and 3 models for simulating interfering discharges in air. The discharge features were analyzed using a 3-D pattern chart with a three-layer back-propagation artificial neural network used to recognize the patterns. The results show that PDs in air and oil can be distinguished. The model can be used for interference rejection on-line monitoring of partial discharge in transformers.
出处 《Tsinghua Science and Technology》 SCIE EI CAS 2005年第5期598-604,共7页 清华大学学报(自然科学版(英文版)
基金 Supported by the National Natural Science Foundation of China, the Northeastern Electric Power Corp. (Group) (No. 59637200), and the National Foundation of USA
关键词 on-line monitoring partial discharge DIAGNOSTIC TRANSFORMER on-line monitoring partial discharge diagnostic transformer
  • 相关文献

同被引文献31

  • 1秦文明.变压器局部放电的超声波定位方法[J].变压器,1995,32(3):6-8. 被引量:11
  • 2宋杲,崔景春,袁大陆.2004年高压开关设备运行统计分析[J].电力设备,2006,7(2):10-14. 被引量:46
  • 3陈庆国,王永红,高文胜,魏新劳,谈克雄.油中局部放电UHF频带选取及干扰的抑制[J].电机与控制学报,2006,10(2):147-150. 被引量:7
  • 4王成江,贾智斌,顾玉凯,杨溢.非合成绝缘子内部放电声发射试验及分析[J].中国电机工程学报,2006,26(10):146-151. 被引量:8
  • 5刘君华,王江,钱勇,段大鹏,黄成军,曾奕,江秀臣.GIS中电磁波传播特性的仿真研究[J].高电压技术,2007,33(8):139-142. 被引量:35
  • 6Lim K J, Kang S H, Lee K W, et al. Partial discharge signal detection by piezoelectric ceramic sensor and the signal processing[J]. Journal of Electroceramics, 2004, 13(2): 487-492.
  • 7Lundgaard L E. Partial discharge-part ⅩⅢ: acoustic partial discharge detection-fundamental considerations[J]. IEEE Electrical Insulation Magazine, 1992, 8(4): 25-31.
  • 8Sakoda T, Nieda H, Ando K. Characteristics of elastic waves caused by corona discharges in an oil-immersed pole transformer[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2001, 8(2):276-283.
  • 9Wang Anbo, Pickrell G R. Optical sensor research at Virginia Tech Center for photonics technology[C]. SPIE-Fiber Optic Sensor Technology and Applications, Glasgow, Britain, 2001.
  • 10Zargari A, Trevor R B. Application of optical fibre sensor for partial discharge detection in high-voltage power equipment[C]. IEEE Annual Report-Conference on Electrical Insulation and Dielectric Phenomena,San Francisco, USA, 1996.

引证文献3

二级引证文献32

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部