摘要
在高压变压器的现场安装时,降低变压器绝缘油中含气量是一项重要环节,也是评价变压器安装质量的一项重要指标。笔者针对现场实际并经实践提出对充氮保管的变压器,在通常的安装流程中,增加连续抽真空(首次注油前)48h及以上,最终可使绝缘油中含气量有明显的下降作用。
Decreasing the gas content in insulating oil of transformer is very important during installalion on site, which is also an important index to evaluate the quality of instullation, In real practice, for a transformer filled with nitrogen in preservation, vacuum is taken out continuously (for the first time before infusing oil) for 48 hours or more, It is considered that this method is helpful in reducing the gas content of insulating oil.
出处
《高压电器》
EI
CAS
CSCD
北大核心
2005年第5期397-398,共2页
High Voltage Apparatus
关键词
变压器
绝缘油
含气量
transformer
insulating oil
gas content