期刊文献+

雷击输电线路电磁暂态仿真 被引量:20

New Electromagnetic Transient Simulation Approach Considering Impulsive Corona and Frequency-dependence Line Parameters
在线阅读 下载PDF
导出
摘要 雷击输电线路会引起强烈的冲击电晕,目前常用的电磁暂态仿真软件中没有冲击电晕的模型,无法对其进行仿真。通过对冲击电晕的伏库特性的分析,得到冲击电晕的等效电路,并与现有比较成熟的Marti线路模型相结合,提出了一种既考虑冲击电晕又考虑线路参数频变的电磁暂态仿真方法。通过雷击输电线路的电磁暂态仿真表明,有否考虑冲击电晕其电晕的电磁暂态过程相差很大,在研究行波保护的雷电波抗干扰方法以及线路、变电站的过电压计算时应该考虑冲击电晕对电磁暂态过程的影响。 Lightning strike on transmission lines brings about intense impulsive corona. However, in many currently available electromagnetic transient simulation software packages, such as EMTP, EMTDC, MATLAB, model of impulsive corona is not included, that results in difficulty to simulate impulsive corona by using those software packages. Hence, in this paper the equivalent circuit of impulsive corona is derived based on the analysis of V-Q characteristic of impulsive corona. Furthermore, a electromagnetic transient simulation method considering both impulsive corona and frequency-dependence line parameters is presented by combining existing and mature Marti model. Large amount of simulations show that the results considering corona are quite different with those without taking account of corona. Therefore the paper concludes that the influence of impulsive corona should be considered in the study of the lightning strike on lines.
出处 《电力系统自动化》 EI CSCD 北大核心 2005年第17期68-71,92,共5页 Automation of Electric Power Systems
基金 国家自然科学基金资助项目(50347026 50467002)云南省科技攻关项目(2003GG10)云南省应用基础研究项目(2002E0025M 2004E0020M)~~
关键词 冲击电晕 电磁暂态仿真 输电线路 impulsive corona electromagnetic transient simulation transmission line
  • 相关文献

参考文献7

  • 1AMENTANI A, KASAI Y, SAWADA J et al.Frequency-dependent Impedance of Vertical Conductors and Multi-conductor Tower Model. IEE Proceedings Generation, Transmission and Distribution, 1994, 141 (4) :339 - 345.
  • 2HUMPAGE W D, WONG K P, NGUYEN T T et al.z-Transform Electromagnetic Transient Analysis in Power System. IEE Proceedings-Generation, Transmission and Distribution, 1980, 127(6): 370-378.
  • 3RAMIREZ A I, SEMLYEN A, IRAVANI R. Modeling Nonuniform Transmission Lines for Time Domain Simulation of Electromagnetic Transients. IEEE Trans on Power Delivery,2003, 18(3): 968-974.
  • 4徐政.耦合长线电磁暂态分析的扩展Bergeron模型[J].中国电机工程学报,1996,16(5):354-357. 被引量:22
  • 5戴玉松,颜怀梁.考虑冲击电晕时的一种多相线等值电路模型[J].中国电机工程学报,1997,17(5):339-343. 被引量:13
  • 6李海锋,王钢,赵建仓.输电线路感应雷击暂态特征分析及其识别方法[J].中国电机工程学报,2004,24(3):114-119. 被引量:79
  • 7NARITA T, YAMADA T, ZAIMA E et al. Observation of Current Wave Shapes of Lightening Strokes on Transmission Towers. IEEE Trans on Power Delivery, 2000, 15(1): 429-435.

二级参考文献10

  • 1丘毓昌 施围 等.高电压工程[M].西安:西安交通大学出版社,1995..
  • 2吴维韩,电力系统过电压数值计算,1989年
  • 3吴维韩,高电压技术,1981年,4期,9页
  • 4吴维韩,电力系统过电压数值计算,1989年
  • 5陈恕行,偏微分方程概论,1981年
  • 6李荣华,偏微分方程的数值解,1980年
  • 7团体著者,偏微分方程,1979年
  • 8团体著者,偏微分方程的数值解,1979年
  • 9福雪斯 G E,偏微分方程的有限差分方法,1979年
  • 10林湘宁,刘沛,杨春明,刘世明.基于小波分析的超高压输电线路无通信全线速动保护方案[J].中国电机工程学报,2001,21(6):9-14. 被引量:63