摘要
本文详细报告了350kW直燃两效溴化锂吸收式冷温水机的开发研究情况:采用了较为新颖的结构和控制系统,给出了试验系统,测试了大量设计工况和变工况数据。机组实测制冷工况的热力系数>1,取暖工况的热力系数>0.9。
This paper detailed reports a development investigation situation for 350 kW direct com-busitibility model double effects lithium Bromide absorption cold lukewarm water engine: it adopt more new structure &. control system, presents experimental system, test mass data of design &- transform design condition, The equipment measured thermodynamic coefficient> 1 for refrigeration condition and thermodynamic coefficient >0. 9 for heating condition.
出处
《制冷》
1994年第2期16-21,共6页
Refrigeration