单室火灾水喷淋灭火的数值研究(英文) 被引量:7

Numerical Study of Water Spray Suppression of Single Room Fire by Zone Model
在线阅读 下载PDF
导出
摘要 建立了单室火灾区域模型 ,模型中考虑了火焰与喷淋水之间的相互作用 .定义了一个称为有效喷淋系数的参数 ,其物理意义为喷淋面积与着火面积的有效比 .对有效喷淋系数和喷淋水流率对灭火效果的影响进行了研究 .通过数值模拟得到了以下结果 :对一定条件下的火灾进行喷淋灭火时 ,分别存在一个临界流量和最大流量 .为了灭火 ,喷淋水流率必须大于临界流量 .但用太大的喷淋水量 ,并不提高灭火效果 ,由于喷淋水过量 ,增加了灭火的运行成本 .在给出条件下 ,临界流量和最大流量分别为 0 .0 5 2 4kg/s和 0 .2kg/s . Single room fire zone model is built. The fire in which the suppressing effect of water sprays is taken into account is simulated. A new spray parameter is defined as effective spray coefficient, which physically stands for the effective ratios between spray area and fire area. The effects of effective spray coefficient and water spray flow rate on fire suppression mechanism are investigated. The simulations show that there are both a critical and a maximum value of water flow rates for a certain fire. To suppress a certain fire, the water spray flow rate must be more than a certain critical value. However, using too high water spray flow rate does not increase fire suppression efficiency but only leads to increased operational cost because of the excess water flow rate. These values are 0.0524 kg/s and 0.2 kg/s respectively.
出处 《燃烧科学与技术》 EI CAS CSCD 2004年第4期308-313,共6页 Journal of Combustion Science and Technology
关键词 水喷淋 有效喷淋系数 区域模型 火灾控制 Fire control systems Mathematical models Models Water
  • 相关文献

参考文献12

  • 1FDS programs. http: // fast. nist. gov/fmabbs. html [ EB/OL]: 16-20.
  • 2Hua J S, Kumar K, Khoo B C, et al. A numerical study of the interaction of water spray with a fire plume[J]. Fire Safety Journal, 2002,37 ( 7 ): 631-657.
  • 3Vaari J. A transient one-zone computer model for total flooding water mist fire suppression in ventilated enclosures[J].Fire Safety Journal, 2002,37 (3) :229-257.
  • 4Nam S. Numerical simulation of the penetration capability of sprinkler sprays [J]. Fire Safety Journal, 1999,32: 307-329.
  • 5Hamins A, McGrattan K B. Reduced-scale experiments to characterize the suppression of rack storage commodity fires[R]. Technical Report NIST Internal report (NISTIR6439), National Institute of Standards and Technology, Gaithersburg, Maryland 20899,1999,1-
  • 6Yu H Z, Lee J L, Kung H C. Suppression of rack-storage fires by water[ A]. In: Fire Safety Science-Proceedings of the fourth international symposium, international association for fire safety science [ C ]. Ottawa, Ontario, 1994, 901-912.
  • 7Kung H C. Development of residential sprinklers and issues highlighted by recent research [ A]. In: Proceedings of 15th Meeting of the UJNR Panel of Fire Research and Safety[ C].San Antonio, TX, 2000, 289-298.
  • 8Forney Glenn P, McGrattan Kevin B. Computing the effect of sprinkler sprays on fire induced gas flow[ A]. In :Proceedings of International Conference on Fire Research and Engineering[C]. Orlando, FL, 1995, 59-64.
  • 9Heskestad G. Scaling the interaction of water sprays and flames [J]. Fire Safety Journal, 2002,37 (6): 535-548.
  • 10Prasad K, Patnaik G, Kailasanath K. A numerical study of water-mist suppression of large scale compartment fires[J]. Fire Safety Journal, 2002, 37 (6) :569-589.