The N3 power plant of Taipower is located in the southern tip of Taiwan and connected to the power pool by four out-linking 345-kV overhead transmission circuits. There are two 951-MW generators. Each generator occupi...The N3 power plant of Taipower is located in the southern tip of Taiwan and connected to the power pool by four out-linking 345-kV overhead transmission circuits. There are two 951-MW generators. Each generator occupied 11% of the system peak load in 1985 when the generator was in commercial operation. Since Taipower is an isolated system, at the N-2 conditions, those generators were reduced to 75% loading to protect the power system. By the way, to avoid damage of negative sequence current (NSC), the limits of the N3 power plant are stricter than those in the IEEE Standard. However, in 2010, the capacity ratio of each generator in the plant to the system peak load has been reduced to 3% only. To increase the economic benefit of those generators, it is required to reassess the operation limits of NSC. EMTP was used to calculate the levels of NSC from the out-linking transmission circuits. From the results of this study, the effects of NSC could be ignored when the four out-linking circuits are in N-0, N-1, and N-2 conditions. The generators can be operated in full loading under these conditions. The modifications to the NSC limits of the N3 power plant are also suggested.展开更多
In many countries,the negative sequence current control(NSCC)has been the national standard for connecting renewable energy to power systems.At the same time,the original relationship of voltage source converters(VSCs...In many countries,the negative sequence current control(NSCC)has been the national standard for connecting renewable energy to power systems.At the same time,the original relationship of voltage source converters(VSCs),commonly used in renewable power generation,shows inherent periodic time-varying characteristics.Considering the pros and cons of the different small-signal models for nonlinear time-varying systems,the comprehensive analysis based on linear time periodic(LTP)and harmonic state-space(HSS)models are introduced to studying the small-signal stability of power systems dominated by VSCs with NSCC.Considering the advantages of the LTP model in stability determination,the stable domains of control parameters are described.Additionally,the structural effect of the decoupled double synchronous reference frame(DDSRF),widely used for separating positive and negative sequences,is compared.Then,considering that the HSS model is a linear time-invariant(LTI)model,and its stability mechanism analysis method is mature,we characterize the interaction among controls based on the participation factor analysis.These comprehensive analysis results are beneficial for understanding the impact of NSCC on system dynamics and provide theoretical support for the optimization of NSCC and DDSRF.Finally,case studies validate the effectiveness of the analysis results.展开更多
Voltage sag is one of the most common power quality disturbances in industry,which causes huge inrush currents in stator windings of induction motors,and adversely impacts the motor secure operation.This paper firstly...Voltage sag is one of the most common power quality disturbances in industry,which causes huge inrush currents in stator windings of induction motors,and adversely impacts the motor secure operation.This paper firstly introduces a 2D Time-Stepping multi-slice finite element method(2D T-S multi-slice FEM)which is used for calculating the magnetic field distribution in induction motors under different sag events.Then the paper deduces the transient analytical expression of stator inrush current based on the classical theory of AC motors and presents a separation method for the positive,negative and zero sequence values based on instantaneous currents.With this method,the paper studies the influences of voltage sag amplitude,phase-angle jump and initial phase angle on the stator positive-and negative-sequence peak currents of 5.5 kW and 55 kW induction motors.This paper further proposes a motor protection method under voltage sag condition with the stator negative-sequence peak currents as the protection threshold,so that the protection false trip can be avoided effectively.Finally,the calculation and analysis results are validated by the comparison of calculated and measured stator peak value of the 5.5 kW induction motor.展开更多
Single-phase low current grounding faults areoften seen in power distribution system of coal mines.These faults are difficult to reliably identify.We propose a new method of single-phase ground fault protection based ...Single-phase low current grounding faults areoften seen in power distribution system of coal mines.These faults are difficult to reliably identify.We propose a new method of single-phase ground fault protection based upon a discernible matrix of the fractal dimension associated with line currents.The method builds on existing selective protection methods.Faulted feeders are distinguished using differences in the zero-sequence transient current fractal dimension.The current signals were first processed through a fast Fourier transform and then the characteristics of a faulted line were identified using a discernible matrix.The method of calculation is illustrated.The results show that the method involves simple calculations, is easy to do and is highly accurate.It is, therefore, suitable for distribution networks having different neutral grounding modes.展开更多
A novel control strategy for three-phase shunt active power filter (SAPF) was proposed to improve its performance under non-ideal mains voltages. The approach was inspired by our finding that the classic instantaneous...A novel control strategy for three-phase shunt active power filter (SAPF) was proposed to improve its performance under non-ideal mains voltages. The approach was inspired by our finding that the classic instantaneous reactive power theory based algorithm was unsatisfactory in terms of isolating positive sequence fundamental active components exactly under non-ideal mains voltages. So, a modified ip-iq reference current calculation method was presented. With usage of the new method, not only the positive sequence but also the fundamental active current components can be accurately isolated from load current. A deadbeat closed-loop control model is built in order to eliminate both delay error and tracking error between reference voltages and compensation voltages under unbalanced and distorted mains voltages. Computer simulation results show that the proposed strategy is effective with better tracking ability and lower total harmonic distortion (THD). The strategy is also applied to a 10 kV substation with a local electrolysis manganese plant injecting a large amount of harmonics into the power system, and is proved to be more practical and efficient.展开更多
The way of neutral point to earth via full compensation arc suppression coil can solve the problem of residual current compensation in coal mine power network effectively. Based on the analysis on the grounding curren...The way of neutral point to earth via full compensation arc suppression coil can solve the problem of residual current compensation in coal mine power network effectively. Based on the analysis on the grounding current detection results of Xieqiao coal mine, the conclusion that harmonic component of grounding current is dominated by higher harmonics with complex harmonic sources in coal mine power network system was obtained. The influences of harmonic source type and fault point position on harmonic voltage and harmonic current were analyzed theoretically. The influences of earthed fault feeder detection result and the estimation errors of parameters to earth on residual current compensation were analyzed. A new thought of residual current prediction and the selections of model method and control method were proposed on this basis. The simulation results prove that harmonic amplitudes of zero sequence voltage and zero sequence current are determined by harmonic source type as well as fault point position in coal mine power network, and also prove that zero sequence voltage detection can avoid the unstable problem of coal mine power network system caused by undercompensation of capacitive current. Finally, the experimental device of full compensation arc suppression coil is introduced.展开更多
文摘The N3 power plant of Taipower is located in the southern tip of Taiwan and connected to the power pool by four out-linking 345-kV overhead transmission circuits. There are two 951-MW generators. Each generator occupied 11% of the system peak load in 1985 when the generator was in commercial operation. Since Taipower is an isolated system, at the N-2 conditions, those generators were reduced to 75% loading to protect the power system. By the way, to avoid damage of negative sequence current (NSC), the limits of the N3 power plant are stricter than those in the IEEE Standard. However, in 2010, the capacity ratio of each generator in the plant to the system peak load has been reduced to 3% only. To increase the economic benefit of those generators, it is required to reassess the operation limits of NSC. EMTP was used to calculate the levels of NSC from the out-linking transmission circuits. From the results of this study, the effects of NSC could be ignored when the four out-linking circuits are in N-0, N-1, and N-2 conditions. The generators can be operated in full loading under these conditions. The modifications to the NSC limits of the N3 power plant are also suggested.
基金supported in part by the National Natural Science Foundation of China under Grant U22B20122 and U23B20120。
文摘In many countries,the negative sequence current control(NSCC)has been the national standard for connecting renewable energy to power systems.At the same time,the original relationship of voltage source converters(VSCs),commonly used in renewable power generation,shows inherent periodic time-varying characteristics.Considering the pros and cons of the different small-signal models for nonlinear time-varying systems,the comprehensive analysis based on linear time periodic(LTP)and harmonic state-space(HSS)models are introduced to studying the small-signal stability of power systems dominated by VSCs with NSCC.Considering the advantages of the LTP model in stability determination,the stable domains of control parameters are described.Additionally,the structural effect of the decoupled double synchronous reference frame(DDSRF),widely used for separating positive and negative sequences,is compared.Then,considering that the HSS model is a linear time-invariant(LTI)model,and its stability mechanism analysis method is mature,we characterize the interaction among controls based on the participation factor analysis.These comprehensive analysis results are beneficial for understanding the impact of NSCC on system dynamics and provide theoretical support for the optimization of NSCC and DDSRF.Finally,case studies validate the effectiveness of the analysis results.
基金This work was supported in part by the National Natural Science Foundation of China under Grant51307050。
文摘Voltage sag is one of the most common power quality disturbances in industry,which causes huge inrush currents in stator windings of induction motors,and adversely impacts the motor secure operation.This paper firstly introduces a 2D Time-Stepping multi-slice finite element method(2D T-S multi-slice FEM)which is used for calculating the magnetic field distribution in induction motors under different sag events.Then the paper deduces the transient analytical expression of stator inrush current based on the classical theory of AC motors and presents a separation method for the positive,negative and zero sequence values based on instantaneous currents.With this method,the paper studies the influences of voltage sag amplitude,phase-angle jump and initial phase angle on the stator positive-and negative-sequence peak currents of 5.5 kW and 55 kW induction motors.This paper further proposes a motor protection method under voltage sag condition with the stator negative-sequence peak currents as the protection threshold,so that the protection false trip can be avoided effectively.Finally,the calculation and analysis results are validated by the comparison of calculated and measured stator peak value of the 5.5 kW induction motor.
基金Project 50504015 supported by the National Natural Science Foundation of Chinathe Youth Science and Technology Research Program of China University of Mining and Technology (0C060996)
文摘Single-phase low current grounding faults areoften seen in power distribution system of coal mines.These faults are difficult to reliably identify.We propose a new method of single-phase ground fault protection based upon a discernible matrix of the fractal dimension associated with line currents.The method builds on existing selective protection methods.Faulted feeders are distinguished using differences in the zero-sequence transient current fractal dimension.The current signals were first processed through a fast Fourier transform and then the characteristics of a faulted line were identified using a discernible matrix.The method of calculation is illustrated.The results show that the method involves simple calculations, is easy to do and is highly accurate.It is, therefore, suitable for distribution networks having different neutral grounding modes.
基金Project(JC200903180555A) supported by Shenzhen City Science and Technology Plan, China
文摘A novel control strategy for three-phase shunt active power filter (SAPF) was proposed to improve its performance under non-ideal mains voltages. The approach was inspired by our finding that the classic instantaneous reactive power theory based algorithm was unsatisfactory in terms of isolating positive sequence fundamental active components exactly under non-ideal mains voltages. So, a modified ip-iq reference current calculation method was presented. With usage of the new method, not only the positive sequence but also the fundamental active current components can be accurately isolated from load current. A deadbeat closed-loop control model is built in order to eliminate both delay error and tracking error between reference voltages and compensation voltages under unbalanced and distorted mains voltages. Computer simulation results show that the proposed strategy is effective with better tracking ability and lower total harmonic distortion (THD). The strategy is also applied to a 10 kV substation with a local electrolysis manganese plant injecting a large amount of harmonics into the power system, and is proved to be more practical and efficient.
基金The financial support from the National Natural Science Foundation of China (No. 51107143)
文摘The way of neutral point to earth via full compensation arc suppression coil can solve the problem of residual current compensation in coal mine power network effectively. Based on the analysis on the grounding current detection results of Xieqiao coal mine, the conclusion that harmonic component of grounding current is dominated by higher harmonics with complex harmonic sources in coal mine power network system was obtained. The influences of harmonic source type and fault point position on harmonic voltage and harmonic current were analyzed theoretically. The influences of earthed fault feeder detection result and the estimation errors of parameters to earth on residual current compensation were analyzed. A new thought of residual current prediction and the selections of model method and control method were proposed on this basis. The simulation results prove that harmonic amplitudes of zero sequence voltage and zero sequence current are determined by harmonic source type as well as fault point position in coal mine power network, and also prove that zero sequence voltage detection can avoid the unstable problem of coal mine power network system caused by undercompensation of capacitive current. Finally, the experimental device of full compensation arc suppression coil is introduced.