With increasing the number of wind power generators,the consumption time of electromagnetic simulation of the wind farm explodes.To reduce the simulation time while meeting the accuracy requirement,a genetic clusterin...With increasing the number of wind power generators,the consumption time of electromagnetic simulation of the wind farm explodes.To reduce the simulation time while meeting the accuracy requirement,a genetic clustering-based equivalent model is proposed for the wind farm with numerous doubly fed induction generators.In the proposed model,active power together with the reactive power and the wind speed are selected to form the set of clustering indicators.A normalization technique is utilized to cope with the multiple orders of magnitude in these factors.An exponential fitness value is formulated as a function of the sorting number of the primary fitness value,and the fitness-based selection probability is constructed to overcome the property of premature and slow convergence of the genetic clustering algorithm.The sum of squares due to error is used to determine the optimal clustering number.In addition,a decoupled parameter equivalence method is adopted to obtain the equivalent parameters of the collection network.Simulation results and comparisons with various methods under different voltage scenarios show the feasibility and effectiveness of the proposed model.展开更多
With the rapid increase of wind farms,the grid code needs to be improved to meet the requirement of wind farms and enhance grid stability.Doubly-fed induction generators are largely used in wind turbines,but they are ...With the rapid increase of wind farms,the grid code needs to be improved to meet the requirement of wind farms and enhance grid stability.Doubly-fed induction generators are largely used in wind turbines,but they are very sensitive to grid disturbances.The voltage swell can be caused by switching on capacitor banks or switching off large loads,which may result in the reversal of the power flow in the grid convertor;the current may flow from the grid into the DC link,which may step up DC voltage,and result in large faults of rotor currents and instantaneous power oscillation.The grid reactive compensation devices can not have the automatic swithing function after the low voltage fault,which will result in local reactive power surplus,so some wind power generators will retreat from the grid under high voltage protection.展开更多
In this paper,rotor of switched reluctance motor(SRM)is employed by mounting copper windings on the rotor poles as well as the stator poles.Rotor and stator windings are excited from DC supply in order to increase the...In this paper,rotor of switched reluctance motor(SRM)is employed by mounting copper windings on the rotor poles as well as the stator poles.Rotor and stator windings are excited from DC supply in order to increase the developed electro-magnetic torque;thus enhancing the output power of the drive and keeping the system compactness.Furthermore,the proposed SRM offers higher reliability than conventional one,if excitation of rotor windings is lost,the drive will turn into a conventional SRM,the drive will continue running as a conventional SRM.Finite element method magnetics(FEMM)software is applied to obtain the magnetic characteristics of the proposed SRM.A control strategy for excitation of rotor and stator windings is presented.MATLAB/Simulink modeling of the proposed SRM is given and validated by practical experiment.Experimental Results on a prototype show that the proposed SRM is capable of achieving an increased torque compared with conventional SRM drive.展开更多
This article proposes a dual-negative-objective coordinated control strategy for brushless doubly fed induction generator(BDFIG)based wind power generation system under unbalanced grid voltage.To alleviate the mechani...This article proposes a dual-negative-objective coordinated control strategy for brushless doubly fed induction generator(BDFIG)based wind power generation system under unbalanced grid voltage.To alleviate the mechanical stress and impaction on rotating shaft,the negative control objective(NCO)of machine side converter(MSC)is set to suppress the ripple of electromagnetic torque.While the NCO of grid side converter(GSC)is selected to suppress the oscillation of total output active power or the unbalanced degree of total output current for BDFIG generation system.In comparison with traditional single converter control scheme of the MSC or GSC,dual NCOs can be satisfied at the same time due to the enlarged freedom degree in the proposed improved coordinated control system for back-toback converters.The effectiveness of proposed control strategy is validated by simulation and experimental results on a dual-cagerotor BDFIG(DCR-BDFIG)prototype.展开更多
The unbalanced voltages cause negative effects on the doubly fed induction generator (DFIG) sucn as torque pulsation,and increased stator current. Based on the symmetrical component theory, the torque pulsation is t...The unbalanced voltages cause negative effects on the doubly fed induction generator (DFIG) sucn as torque pulsation,and increased stator current. Based on the symmetrical component theory, the torque pulsation is the consequence of the interaction of stator and rotor currents of different sequences. This paper presents a control technique to reduce the effect of unbalanced voltages on the DFIG in wind energy conversion systems. The negative sequence stator voltage is derived from the unbalanced three phase stator voltages. The compensated rotor voltage in terms of the derived negative sequence stator voltage and slip which minimizes the negative stator and rotor currents is proposed. The results from the simulation of control system with steady state model and dynamic model of the DFIG show that additional control loop with compensated voltage can significantly reduce torque and reactive power pulsations.展开更多
Subsynchronous resonance(SSR)and high-frequency resonance(HFR)are two phenomena that exist in a doubly fed induction generator(DFIG)system operated in a weak grid.Besides the aforementioned resonance,dead-time in the ...Subsynchronous resonance(SSR)and high-frequency resonance(HFR)are two phenomena that exist in a doubly fed induction generator(DFIG)system operated in a weak grid.Besides the aforementioned resonance,dead-time in the converter(rotor side converter(RSC)and grid side converter(GSC))of the DFIG system can cause resonance at middle frequencies.The aforementioned resonance at middle frequencies can greatly degrade dynamic performance and cause instabilities in the DFIG system.Nevertheless,there is not enough research available in existing literature on resonance in the DFIG system,considering dead-time impact.This paper proposes a new method of resonance analysis in a DFIG system,taking dead-time effect into consideration and utilizing small-signal impedance modeling.Dead-time of the RSC and GSC will introduce distorted voltage into the rotor-and stator-side of the DFIG.Then,rotor-side impedance is modified by adding the effect of transfer function(impedance)from the distorted voltage to rotor current.Likewise,the stator-side impedance is modified by adding the effect of the transfer function(impedance)from distorted voltage to stator current.Thus,overall DFIG system impedance,as seen from the point of common coupling is changed.Finally,resonance is revealed by plotting the DFIG system impedance and weak grid impedance on the Bode plot.Additionally,resonance mitigation is impedance on the Bode plot.Additionally,resonance mitigation is exposed through the dead-time compensation(DTC)technique using an adaptive second-order bandpass filter.With the proposed technique,the resonance at middle frequencies is damped with zero probability of resonance reoccurrence.Finally,the validity and the accuracy of the proposed DTC techniques are validated using mathematical analysis and simulations in Matlab.展开更多
In multi-fed grid-connected systems,there are complex dynamic interactions between different pieces of equipment.Particularly in situations of weak-grid faults,the dynamic coupling between equipment becomes more prono...In multi-fed grid-connected systems,there are complex dynamic interactions between different pieces of equipment.Particularly in situations of weak-grid faults,the dynamic coupling between equipment becomes more pronounced.This may cause the system to experience small-signal instability during the fault steady-state.In this paper,multi-paralleled doubly fed induction generator(DFIG)-based wind farms(WFs)are taken as an example to study the dynamic coupling within a multi-fed system during fault steady-state of symmetrical low voltage ride-through(LVRT)in a weak grid.The analysis reveals that the dynamic coupling between WFs will introduce a damping shift to each WF.This inevitably affects the system’s dynamic stability and brings the risk of small-signal instability during fault steady-state in LVRT scenarios.Increasing the distance to fault location and fault severity will exacerbate the dynamic coupling between WFs.Because of the dynamic coupling,adjusting the control state of one WF will affect the stability of the remaining WFs in the system.Hence,a cooperative control strategy for multi-paralleled DFIG WFs is proposed to improve dynamic stability during LVRT.The analysis and the effectiveness of the proposed control strategy are verified by modal analysis and simu-lation.展开更多
This paper discusses the robust control of a grid-connected doubly-fed induction generator (DFIG) controlled by vector control using a nonlinear feedback linearization strategy in order to ameliorate the performance...This paper discusses the robust control of a grid-connected doubly-fed induction generator (DFIG) controlled by vector control using a nonlinear feedback linearization strategy in order to ameliorate the performances of the control and to govern the developed stator active and reactive power in a linear and decoupled manner, in which an optimal operation of the DFIG in subsynchronous operation is given, as well as the control stator power flow with the possibility of keeping stator power factor at a unity. The use of the state-all-flux induction machine model gives place to a simpler control model. So, to achieve this objective, the Lyapunov approach is used associated with a sliding mode control to guarantee the global asymptotical stability and the robustness of the parametric variations.展开更多
This paper presents a multiple target implementation technique for a doubly fed induction generator (DFIG) under unbalanced and distorted grid voltage based on direct power control (DPC). Based on the mathematical...This paper presents a multiple target implementation technique for a doubly fed induction generator (DFIG) under unbalanced and distorted grid voltage based on direct power control (DPC). Based on the mathematical model of DFIG under unbalanced and distorted voltage, the proportional and integral (PI) regulator is adopted to regulate the DFIG average active and reactive powers, while the vector P1 (VPI) resonant regulator is used to achieve three alternative control targets: (1) balanced and sinusoidal stator current; (2) smooth instantaneous stator active and reactive powers; (3) smooth electromagnetic torque and instantaneous stator reactive power. The major advantage of the proposed control strategy over the conventional method is that neither negative and harmonic sequence decomposition of grid voltage nor complicated control reference calculation is required. The insensitivity of the proposed control strategy to DFIG parameter deviation is analyzed. Finally, the DFIG experimental system is developed to validate the availability of the proposed DPC strategy under unbalanced and distorted grid voltage,展开更多
This article presents the direct torque control (DTC) strategy for the doubly fed induction motor (DFIM) connected to two three-level voltage source inverters (3LVSIs) with neutral point clamped (NPC) structure. This ...This article presents the direct torque control (DTC) strategy for the doubly fed induction motor (DFIM) connected to two three-level voltage source inverters (3LVSIs) with neutral point clamped (NPC) structure. This control method allows to reduce the torque and flux ripples as well as to optimize the total harmonic distortion (THD) of motor currents. The use of 3LVSI increases the number of generated voltage, which allows improving the quality of its waveform and thus improves the DTC strategy. The system modeling and control are implemented in Matlab/Simulink environment. The analysis of simulation results shows the better performances of this control, especially in terms of torque and flux behavior, compared to conventional DTC.展开更多
This paper deals with robust direct power control of a grid-connected bmshless doubly-fed induction generator(BDFIG). Using a nonlinear feedback lineariza- tion strategy, an attempt is made to improve the desired pe...This paper deals with robust direct power control of a grid-connected bmshless doubly-fed induction generator(BDFIG). Using a nonlinear feedback lineariza- tion strategy, an attempt is made to improve the desired performances by controlling the generated stator active and reactive power in a linear and decoupled manner. There- fore, to achieve this objective, the Lyapunov approach is used associated with a sliding mode control to guarantee the global asymptotical stability. Thus, an optimal operation of the BDFIG in sub-synchronous operation is obtained as well as the stator power flows with the possibility of keeping stator power factor at a unity. The proposed method is tested with the Matlab/Simulink software. Simulation results illustrate the performances and the feasibility of the designed control.展开更多
A robust optimal framework is designed herein to mitigate the oscillatory dynamics in a doubly fed induction generator(DFIG)even in the presence of network disturbances and input variation.To address uncertain dynamic...A robust optimal framework is designed herein to mitigate the oscillatory dynamics in a doubly fed induction generator(DFIG)even in the presence of network disturbances and input variation.To address uncertain dynamics,herein,a novel transformation formula is developed for a wind energy conversion system.An unscented Kalman filter is applied to estimate the un-measured internal states of the wind energy conversion system using terminal measurements.The detailed convergence and stability analyses of the presented framework are investigated to validate its effectiveness.Additionally,comparative modal analyses are carried out to demonstrate the improvement in the damping of critical low-frequency oscillatory modes using the presented framework.The simulation results demonstrate satisfactory performance under various operating scenarios,such as increasing and decreasing wind speed and varying the terminal voltage.The comparative performance is demonstrated to validate the effectiveness of the presented framework over that of the state-of-the-art frameworks.展开更多
The amount of electrical energy produced by wind mills is constantly increasing.Nowadays detailed analyzes considering the impact of wind energy integration on the transmission system are required.The goal of this stu...The amount of electrical energy produced by wind mills is constantly increasing.Nowadays detailed analyzes considering the impact of wind energy integration on the transmission system are required.The goal of this study is to investigate the dynamic response of a wind turbine with doubly fed induction generator connected to the power system during grid disturbance.The current and future wind power situation is modeled as two cases and a transient fault is simulated.In order to analyze the impact of wind energy integration in electrical power grid,a power system model has been developed,integrated with wind turbine using doubly fed induction generator and transient analysis are performed.Here,an attempt has been made to compare the impact,in terms of voltages,currents,total harmonic distortion,etc.,of adding wind turbines into electrical power grid.展开更多
Wide-band oscillations have become a significant issue limiting the development of wind power.Both large-signal and small-signal analyses require extensive model derivation.Moreover,the large number and high order of ...Wide-band oscillations have become a significant issue limiting the development of wind power.Both large-signal and small-signal analyses require extensive model derivation.Moreover,the large number and high order of wind turbines have driven the development of simplified models,whose applicability remains controversial.In this paper,a wide-band oscillation analysis method based on the average-value model(AVM)is proposed for wind farms(WFs).A novel linearization analysis framework is developed,leveraging the continuous-time characteristics of the AVM and MATLAB/Simulink’s built-in linearization tools.This significantly reduces modeling complexity and computational costs while maintaining model fidelity.Additionally,an object-based initial value estimation method of state variables is introduced,which,when combined with steady-state point-solving tools,greatly reduces the computational effort required for equilibrium point solving in batch linearization analysis.The proposed method is validated in both doubly fed induction generator(DFIG)-based and permanent magnet synchronous generator(PMSG)-based WFs.Furthermore,a comprehensive analysis is conducted for the first time to examine the impact of the machine-side system on the system stability of the nonfully controlled PMSG-based WF.展开更多
This paper proposes a novel framework that enables the simultaneous coordination of the controllers of doubly fed induction generators(DFIGs) and synchronous generators(SGs).The proposed coordination approach is based...This paper proposes a novel framework that enables the simultaneous coordination of the controllers of doubly fed induction generators(DFIGs) and synchronous generators(SGs).The proposed coordination approach is based on the zero dynamics method aims at enhancing the transient stability of multi-machine power systems under a wide range of operating conditions. The proposed approach was implemented to the IEEE39-bus power systems. Transient stability margin measured in terms of critical clearing time along with eigenvalue analysis and time domain simulations were considered in the performance assessment. The obtained results were also compared to those achieved using a conventional power system stabilizer/power oscillation(PSS/POD) technique and the interconnection and damping assignment passivity-based controller(IDA-PBC). The performance analysis confirmed the ability of the proposed approach to enhance damping and improve system’s transient stability margin under a wide range of operating conditions.展开更多
An integral terminal sliding mode-based control design is proposed in this paper to enhance the power quality of wind turbines under unbalanced voltage conditions. The design combines the robustness, fast response, an...An integral terminal sliding mode-based control design is proposed in this paper to enhance the power quality of wind turbines under unbalanced voltage conditions. The design combines the robustness, fast response, and high quality transient characteristics of the integral terminal sliding mode control with the estimation properties of disturbance observers. The controller gains were auto-tuned using a fuzzy logic approach.The effectiveness of the proposed design was assessed under deep voltage sag conditions and parameter variations. Its dynamic response was also compared to that of a standard SMC approach.The performance analysis and simulation results confirmed the ability of the proposed approach to maintain the active power,currents, DC-link voltage and electromagnetic torque within their acceptable ranges even under the most severe unbalanced voltage conditions. It was also shown to be robust to uncertainties and parameter variations, while effectively mitigating chattering in comparison with the standard SMC.展开更多
In this research paper,an improved strategy to enhance the performance of the DC-link voltage loop regulation in a Doubly Fed Induction Generator(DFIG)based wind energy system has been proposed.The proposed strategy u...In this research paper,an improved strategy to enhance the performance of the DC-link voltage loop regulation in a Doubly Fed Induction Generator(DFIG)based wind energy system has been proposed.The proposed strategy used the robust Fractional-Order(FO)Proportional-Integral(PI)control technique.The FOPI control contains a non-integer order which is preferred over the integer-order control owing to its benefits.It offers extra flexibility in design and demonstrates superior outcomes such as high robustness and effectiveness.The optimal gains of the FOPI controller have been determined using a recent Manta Ray Foraging Optimization(MRFO)algorithm.During the optimization process,the FOPI controller’s parameters are assigned to be the decision variables whereas the objective function is the error racking that to be minimized.To prove the superiority of the MRFO algorithm,an empirical comparison study with the homologous particle swarm optimization and genetic algorithm is achieved.The obtained results proved the superiority of the introduced strategy in tracking and control performances against various conditions such as voltage dips and wind speed variation.展开更多
Renewable energy production plays a major role in satisfying electricity demand.Wind power conversion is one of the most popular renewable energy sources compared to other sources.Wind energy conversion has two major ...Renewable energy production plays a major role in satisfying electricity demand.Wind power conversion is one of the most popular renewable energy sources compared to other sources.Wind energy conversion has two major types of generators such as the Permanent Magnet Synchronous Generator(PMSG)and the Doubly Fed Induction Generator(DFIG).The maximum power tracking algo-rithm is a crucial controller,a wind energy conversion system for generating maximum power in different wind speed conditions.In this article,the DFIG wind energy conversion system was developed in Matrix Laboratory(MATLAB)and designed a machine learning(ML)algorithm for the rotor and grid side converter.The ML algorithm has been developed and trained in a MATLAB environment.There are two types of learning algorithms such as supervised and unsupervised learning.In this research supervised learning is used to power the neural networks and analysis is made for various hidden layers and activation functions.Simulation results are assessed to demonstrate the efficiency of the proposed system.展开更多
The performance of a 1.5 MVA wind-power Doubly Fed Induction Generator (DFIG) under network fault is studied using simulator developed in MATLAB-SIMULINK. This paper investigates a new control method able to improve...The performance of a 1.5 MVA wind-power Doubly Fed Induction Generator (DFIG) under network fault is studied using simulator developed in MATLAB-SIMULINK. This paper investigates a new control method able to improve the fault-ride through capability of DFIG. In such generators the appearance of severe voltage sags at the coupling point make highlight important over currents at the rotor/stator windings, making the use of crowbar protection device necessary and inevitable in order to protect the machine as well as the rotor side power converter. The simulator consists of the DFIG analytical model, power transformer model and the detailed frequency converter model including crowbar protection device. Simulation results are carried out to show the transient behavior of the DFIG when a sudden voltage dip is introduced with and without the crowbar implementation.展开更多
The increased level of penetration of wind generators into modern power system has significant effect on network operation. The time varying nature of wind speed has significant effect on performance of wind generator...The increased level of penetration of wind generators into modern power system has significant effect on network operation. The time varying nature of wind speed has significant effect on performance of wind generator, therefore efficient mechanism for stabilizing the output of the wind generator is very much needed. Self-excited induction generators (SEIG) already existing in the network are sensitive to wind speeds. In this paper, a new method for voltage control of SEIG utilizing reactive power enhancing capabilities of doubly-fed induction generator (DFIG) is simulated and its effect on the network is analyzed for varying wind speeds. The choice of placing DFIG adjacent to SEIG or at another bus is also addressed in this paper with simulation results. The results show that this method of utilizing the reactive power capabilities of DFIG enhances voltage stability of SEIG as well as system stability.展开更多
基金the National Key R&D Program of China(No.2019YFE0114700)the Key R&D Program in Hunan Province of China(No.2021GK2020)+1 种基金the Natural Science Foundation of Hunan Province of China(No.2021JJ30079)the Project of Philosophy and Social Science Research in Yiyang City(No.2022YS191)。
文摘With increasing the number of wind power generators,the consumption time of electromagnetic simulation of the wind farm explodes.To reduce the simulation time while meeting the accuracy requirement,a genetic clustering-based equivalent model is proposed for the wind farm with numerous doubly fed induction generators.In the proposed model,active power together with the reactive power and the wind speed are selected to form the set of clustering indicators.A normalization technique is utilized to cope with the multiple orders of magnitude in these factors.An exponential fitness value is formulated as a function of the sorting number of the primary fitness value,and the fitness-based selection probability is constructed to overcome the property of premature and slow convergence of the genetic clustering algorithm.The sum of squares due to error is used to determine the optimal clustering number.In addition,a decoupled parameter equivalence method is adopted to obtain the equivalent parameters of the collection network.Simulation results and comparisons with various methods under different voltage scenarios show the feasibility and effectiveness of the proposed model.
文摘With the rapid increase of wind farms,the grid code needs to be improved to meet the requirement of wind farms and enhance grid stability.Doubly-fed induction generators are largely used in wind turbines,but they are very sensitive to grid disturbances.The voltage swell can be caused by switching on capacitor banks or switching off large loads,which may result in the reversal of the power flow in the grid convertor;the current may flow from the grid into the DC link,which may step up DC voltage,and result in large faults of rotor currents and instantaneous power oscillation.The grid reactive compensation devices can not have the automatic swithing function after the low voltage fault,which will result in local reactive power surplus,so some wind power generators will retreat from the grid under high voltage protection.
文摘In this paper,rotor of switched reluctance motor(SRM)is employed by mounting copper windings on the rotor poles as well as the stator poles.Rotor and stator windings are excited from DC supply in order to increase the developed electro-magnetic torque;thus enhancing the output power of the drive and keeping the system compactness.Furthermore,the proposed SRM offers higher reliability than conventional one,if excitation of rotor windings is lost,the drive will turn into a conventional SRM,the drive will continue running as a conventional SRM.Finite element method magnetics(FEMM)software is applied to obtain the magnetic characteristics of the proposed SRM.A control strategy for excitation of rotor and stator windings is presented.MATLAB/Simulink modeling of the proposed SRM is given and validated by practical experiment.Experimental Results on a prototype show that the proposed SRM is capable of achieving an increased torque compared with conventional SRM drive.
基金supported in part by National Natural Science Foundation of China under Grant 61973073supported by Jiangsu Province Higher Education Basic Science (Natural Science) Research Project under Grant 23KJB470022
文摘This article proposes a dual-negative-objective coordinated control strategy for brushless doubly fed induction generator(BDFIG)based wind power generation system under unbalanced grid voltage.To alleviate the mechanical stress and impaction on rotating shaft,the negative control objective(NCO)of machine side converter(MSC)is set to suppress the ripple of electromagnetic torque.While the NCO of grid side converter(GSC)is selected to suppress the oscillation of total output active power or the unbalanced degree of total output current for BDFIG generation system.In comparison with traditional single converter control scheme of the MSC or GSC,dual NCOs can be satisfied at the same time due to the enlarged freedom degree in the proposed improved coordinated control system for back-toback converters.The effectiveness of proposed control strategy is validated by simulation and experimental results on a dual-cagerotor BDFIG(DCR-BDFIG)prototype.
文摘The unbalanced voltages cause negative effects on the doubly fed induction generator (DFIG) sucn as torque pulsation,and increased stator current. Based on the symmetrical component theory, the torque pulsation is the consequence of the interaction of stator and rotor currents of different sequences. This paper presents a control technique to reduce the effect of unbalanced voltages on the DFIG in wind energy conversion systems. The negative sequence stator voltage is derived from the unbalanced three phase stator voltages. The compensated rotor voltage in terms of the derived negative sequence stator voltage and slip which minimizes the negative stator and rotor currents is proposed. The results from the simulation of control system with steady state model and dynamic model of the DFIG show that additional control loop with compensated voltage can significantly reduce torque and reactive power pulsations.
基金supported by the National Natural Science Foundation of China(51577025)the Science and Technology Program of State Grid Corporation of China(5100-201999330A-0-0-00).
文摘Subsynchronous resonance(SSR)and high-frequency resonance(HFR)are two phenomena that exist in a doubly fed induction generator(DFIG)system operated in a weak grid.Besides the aforementioned resonance,dead-time in the converter(rotor side converter(RSC)and grid side converter(GSC))of the DFIG system can cause resonance at middle frequencies.The aforementioned resonance at middle frequencies can greatly degrade dynamic performance and cause instabilities in the DFIG system.Nevertheless,there is not enough research available in existing literature on resonance in the DFIG system,considering dead-time impact.This paper proposes a new method of resonance analysis in a DFIG system,taking dead-time effect into consideration and utilizing small-signal impedance modeling.Dead-time of the RSC and GSC will introduce distorted voltage into the rotor-and stator-side of the DFIG.Then,rotor-side impedance is modified by adding the effect of transfer function(impedance)from the distorted voltage to rotor current.Likewise,the stator-side impedance is modified by adding the effect of the transfer function(impedance)from distorted voltage to stator current.Thus,overall DFIG system impedance,as seen from the point of common coupling is changed.Finally,resonance is revealed by plotting the DFIG system impedance and weak grid impedance on the Bode plot.Additionally,resonance mitigation is impedance on the Bode plot.Additionally,resonance mitigation is exposed through the dead-time compensation(DTC)technique using an adaptive second-order bandpass filter.With the proposed technique,the resonance at middle frequencies is damped with zero probability of resonance reoccurrence.Finally,the validity and the accuracy of the proposed DTC techniques are validated using mathematical analysis and simulations in Matlab.
基金the National Natural Science Foundation of China(NSFC)(No.51977019)in part by the Joint Research Fund in Smart Grid under Cooperative Agreement between the National Natural Science Foundation of China(NSFC)(No.U1966208)State Grid Corporation of China(SGCC).
文摘In multi-fed grid-connected systems,there are complex dynamic interactions between different pieces of equipment.Particularly in situations of weak-grid faults,the dynamic coupling between equipment becomes more pronounced.This may cause the system to experience small-signal instability during the fault steady-state.In this paper,multi-paralleled doubly fed induction generator(DFIG)-based wind farms(WFs)are taken as an example to study the dynamic coupling within a multi-fed system during fault steady-state of symmetrical low voltage ride-through(LVRT)in a weak grid.The analysis reveals that the dynamic coupling between WFs will introduce a damping shift to each WF.This inevitably affects the system’s dynamic stability and brings the risk of small-signal instability during fault steady-state in LVRT scenarios.Increasing the distance to fault location and fault severity will exacerbate the dynamic coupling between WFs.Because of the dynamic coupling,adjusting the control state of one WF will affect the stability of the remaining WFs in the system.Hence,a cooperative control strategy for multi-paralleled DFIG WFs is proposed to improve dynamic stability during LVRT.The analysis and the effectiveness of the proposed control strategy are verified by modal analysis and simu-lation.
文摘This paper discusses the robust control of a grid-connected doubly-fed induction generator (DFIG) controlled by vector control using a nonlinear feedback linearization strategy in order to ameliorate the performances of the control and to govern the developed stator active and reactive power in a linear and decoupled manner, in which an optimal operation of the DFIG in subsynchronous operation is given, as well as the control stator power flow with the possibility of keeping stator power factor at a unity. The use of the state-all-flux induction machine model gives place to a simpler control model. So, to achieve this objective, the Lyapunov approach is used associated with a sliding mode control to guarantee the global asymptotical stability and the robustness of the parametric variations.
基金Project supported by the National High-Tech R&D Program(863)of China(No.2011AA050204)the National Natural Science Foundation of China(No.51277159)
文摘This paper presents a multiple target implementation technique for a doubly fed induction generator (DFIG) under unbalanced and distorted grid voltage based on direct power control (DPC). Based on the mathematical model of DFIG under unbalanced and distorted voltage, the proportional and integral (PI) regulator is adopted to regulate the DFIG average active and reactive powers, while the vector P1 (VPI) resonant regulator is used to achieve three alternative control targets: (1) balanced and sinusoidal stator current; (2) smooth instantaneous stator active and reactive powers; (3) smooth electromagnetic torque and instantaneous stator reactive power. The major advantage of the proposed control strategy over the conventional method is that neither negative and harmonic sequence decomposition of grid voltage nor complicated control reference calculation is required. The insensitivity of the proposed control strategy to DFIG parameter deviation is analyzed. Finally, the DFIG experimental system is developed to validate the availability of the proposed DPC strategy under unbalanced and distorted grid voltage,
文摘This article presents the direct torque control (DTC) strategy for the doubly fed induction motor (DFIM) connected to two three-level voltage source inverters (3LVSIs) with neutral point clamped (NPC) structure. This control method allows to reduce the torque and flux ripples as well as to optimize the total harmonic distortion (THD) of motor currents. The use of 3LVSI increases the number of generated voltage, which allows improving the quality of its waveform and thus improves the DTC strategy. The system modeling and control are implemented in Matlab/Simulink environment. The analysis of simulation results shows the better performances of this control, especially in terms of torque and flux behavior, compared to conventional DTC.
文摘This paper deals with robust direct power control of a grid-connected bmshless doubly-fed induction generator(BDFIG). Using a nonlinear feedback lineariza- tion strategy, an attempt is made to improve the desired performances by controlling the generated stator active and reactive power in a linear and decoupled manner. There- fore, to achieve this objective, the Lyapunov approach is used associated with a sliding mode control to guarantee the global asymptotical stability. Thus, an optimal operation of the BDFIG in sub-synchronous operation is obtained as well as the stator power flows with the possibility of keeping stator power factor at a unity. The proposed method is tested with the Matlab/Simulink software. Simulation results illustrate the performances and the feasibility of the designed control.
基金supported in part by the National Natural Science Foundation of China(No.62103296)the UK Engineering and Physical Sciences Research Council(No.EP/T021713/1)the Shanxi Scholarship Council of China(No.2023-062).
文摘A robust optimal framework is designed herein to mitigate the oscillatory dynamics in a doubly fed induction generator(DFIG)even in the presence of network disturbances and input variation.To address uncertain dynamics,herein,a novel transformation formula is developed for a wind energy conversion system.An unscented Kalman filter is applied to estimate the un-measured internal states of the wind energy conversion system using terminal measurements.The detailed convergence and stability analyses of the presented framework are investigated to validate its effectiveness.Additionally,comparative modal analyses are carried out to demonstrate the improvement in the damping of critical low-frequency oscillatory modes using the presented framework.The simulation results demonstrate satisfactory performance under various operating scenarios,such as increasing and decreasing wind speed and varying the terminal voltage.The comparative performance is demonstrated to validate the effectiveness of the presented framework over that of the state-of-the-art frameworks.
文摘The amount of electrical energy produced by wind mills is constantly increasing.Nowadays detailed analyzes considering the impact of wind energy integration on the transmission system are required.The goal of this study is to investigate the dynamic response of a wind turbine with doubly fed induction generator connected to the power system during grid disturbance.The current and future wind power situation is modeled as two cases and a transient fault is simulated.In order to analyze the impact of wind energy integration in electrical power grid,a power system model has been developed,integrated with wind turbine using doubly fed induction generator and transient analysis are performed.Here,an attempt has been made to compare the impact,in terms of voltages,currents,total harmonic distortion,etc.,of adding wind turbines into electrical power grid.
基金supported by the National Natural Science Foundation of China under Grant 52277072.
文摘Wide-band oscillations have become a significant issue limiting the development of wind power.Both large-signal and small-signal analyses require extensive model derivation.Moreover,the large number and high order of wind turbines have driven the development of simplified models,whose applicability remains controversial.In this paper,a wide-band oscillation analysis method based on the average-value model(AVM)is proposed for wind farms(WFs).A novel linearization analysis framework is developed,leveraging the continuous-time characteristics of the AVM and MATLAB/Simulink’s built-in linearization tools.This significantly reduces modeling complexity and computational costs while maintaining model fidelity.Additionally,an object-based initial value estimation method of state variables is introduced,which,when combined with steady-state point-solving tools,greatly reduces the computational effort required for equilibrium point solving in batch linearization analysis.The proposed method is validated in both doubly fed induction generator(DFIG)-based and permanent magnet synchronous generator(PMSG)-based WFs.Furthermore,a comprehensive analysis is conducted for the first time to examine the impact of the machine-side system on the system stability of the nonfully controlled PMSG-based WF.
文摘This paper proposes a novel framework that enables the simultaneous coordination of the controllers of doubly fed induction generators(DFIGs) and synchronous generators(SGs).The proposed coordination approach is based on the zero dynamics method aims at enhancing the transient stability of multi-machine power systems under a wide range of operating conditions. The proposed approach was implemented to the IEEE39-bus power systems. Transient stability margin measured in terms of critical clearing time along with eigenvalue analysis and time domain simulations were considered in the performance assessment. The obtained results were also compared to those achieved using a conventional power system stabilizer/power oscillation(PSS/POD) technique and the interconnection and damping assignment passivity-based controller(IDA-PBC). The performance analysis confirmed the ability of the proposed approach to enhance damping and improve system’s transient stability margin under a wide range of operating conditions.
文摘An integral terminal sliding mode-based control design is proposed in this paper to enhance the power quality of wind turbines under unbalanced voltage conditions. The design combines the robustness, fast response, and high quality transient characteristics of the integral terminal sliding mode control with the estimation properties of disturbance observers. The controller gains were auto-tuned using a fuzzy logic approach.The effectiveness of the proposed design was assessed under deep voltage sag conditions and parameter variations. Its dynamic response was also compared to that of a standard SMC approach.The performance analysis and simulation results confirmed the ability of the proposed approach to maintain the active power,currents, DC-link voltage and electromagnetic torque within their acceptable ranges even under the most severe unbalanced voltage conditions. It was also shown to be robust to uncertainties and parameter variations, while effectively mitigating chattering in comparison with the standard SMC.
文摘In this research paper,an improved strategy to enhance the performance of the DC-link voltage loop regulation in a Doubly Fed Induction Generator(DFIG)based wind energy system has been proposed.The proposed strategy used the robust Fractional-Order(FO)Proportional-Integral(PI)control technique.The FOPI control contains a non-integer order which is preferred over the integer-order control owing to its benefits.It offers extra flexibility in design and demonstrates superior outcomes such as high robustness and effectiveness.The optimal gains of the FOPI controller have been determined using a recent Manta Ray Foraging Optimization(MRFO)algorithm.During the optimization process,the FOPI controller’s parameters are assigned to be the decision variables whereas the objective function is the error racking that to be minimized.To prove the superiority of the MRFO algorithm,an empirical comparison study with the homologous particle swarm optimization and genetic algorithm is achieved.The obtained results proved the superiority of the introduced strategy in tracking and control performances against various conditions such as voltage dips and wind speed variation.
文摘Renewable energy production plays a major role in satisfying electricity demand.Wind power conversion is one of the most popular renewable energy sources compared to other sources.Wind energy conversion has two major types of generators such as the Permanent Magnet Synchronous Generator(PMSG)and the Doubly Fed Induction Generator(DFIG).The maximum power tracking algo-rithm is a crucial controller,a wind energy conversion system for generating maximum power in different wind speed conditions.In this article,the DFIG wind energy conversion system was developed in Matrix Laboratory(MATLAB)and designed a machine learning(ML)algorithm for the rotor and grid side converter.The ML algorithm has been developed and trained in a MATLAB environment.There are two types of learning algorithms such as supervised and unsupervised learning.In this research supervised learning is used to power the neural networks and analysis is made for various hidden layers and activation functions.Simulation results are assessed to demonstrate the efficiency of the proposed system.
文摘The performance of a 1.5 MVA wind-power Doubly Fed Induction Generator (DFIG) under network fault is studied using simulator developed in MATLAB-SIMULINK. This paper investigates a new control method able to improve the fault-ride through capability of DFIG. In such generators the appearance of severe voltage sags at the coupling point make highlight important over currents at the rotor/stator windings, making the use of crowbar protection device necessary and inevitable in order to protect the machine as well as the rotor side power converter. The simulator consists of the DFIG analytical model, power transformer model and the detailed frequency converter model including crowbar protection device. Simulation results are carried out to show the transient behavior of the DFIG when a sudden voltage dip is introduced with and without the crowbar implementation.
文摘The increased level of penetration of wind generators into modern power system has significant effect on network operation. The time varying nature of wind speed has significant effect on performance of wind generator, therefore efficient mechanism for stabilizing the output of the wind generator is very much needed. Self-excited induction generators (SEIG) already existing in the network are sensitive to wind speeds. In this paper, a new method for voltage control of SEIG utilizing reactive power enhancing capabilities of doubly-fed induction generator (DFIG) is simulated and its effect on the network is analyzed for varying wind speeds. The choice of placing DFIG adjacent to SEIG or at another bus is also addressed in this paper with simulation results. The results show that this method of utilizing the reactive power capabilities of DFIG enhances voltage stability of SEIG as well as system stability.