To ensure their sound and continuous operation to the greatest extent,VSC-based DC girds have extremely stringent requirements for transmission line relay protection.In terms of guaranteeing their reliability,accurate...To ensure their sound and continuous operation to the greatest extent,VSC-based DC girds have extremely stringent requirements for transmission line relay protection.In terms of guaranteeing their reliability,accurate identification of lightning strikes on DC transmission lines is one of the urgent key problems to be solved.An effective ultra-high-speed identification scheme of lightning strikes suitable for the VSC-based DC grid is proposed in this paper.First,an 1-mode reverse voltage traveling wave(RVTW)is constructed applying the pole-mode transformation theory.Next,fault traveling wave propagation characteristics along the DC transmission line are analyzed in depth utilizing Peterson's law.Then,differences of time-frequency electromagnetic transient characteristics of 1-mode RVTWs between disturbances and faults caused by lightning strikes are distinguished in detail by means of the classical wavelet transformation multi-resolution analysis theory.Finally,extensive simulations are carried out to evaluate the performance of the proposed identification scheme,and by which its excellent rapidity,reliability and robustness are validated.Index Terms-Lightning-strike identification,Multi-resolution analysis,Relay protection,Traveling-wave protection,VsC-based DC grid,Wavelet transformation.展开更多
Segmentation of large AC systems through DC links introduces a new concept that utilizes the advantages of direct current transmission to improve network reliability and increase power transfer capacity. Technical lit...Segmentation of large AC systems through DC links introduces a new concept that utilizes the advantages of direct current transmission to improve network reliability and increase power transfer capacity. Technical literature argues that the segmentation of the AC network and the introduction of DC links at these systems connection points bring benefits to system operation, once contingencies generated on one side of the DC connection point would not be reflected on the other side of DC connection, thereby reducing the likelihood of cascading shutdowns and blackouts due to load restraint on transmission lines and transformers. Amidst this scenario, this paper presents a study of the main topics regarding the use of this new network segmentation philosophy, bringing a practical point of view for the use of this concept at the electrical power system planning. The effect of DC segmentation before a contingency that would initiate major outages in an adapted electrical system model IEEE-14 bus is studied and simulations have been performed with test HVAC systems and segmented by HVDC link. The results have been compared, principally in relation to the voltage bus, reactive power generation, system losses and power flow at the lines, and demonstrated that this new concept improved the grid reliability.展开更多
The hybrid dc circuit breaker(HCB)has the advantages of fast action speed and low operating loss,which is an idealmethod for fault isolation ofmulti-terminal dc grids.Formulti-terminal dc grids that transmit power thr...The hybrid dc circuit breaker(HCB)has the advantages of fast action speed and low operating loss,which is an idealmethod for fault isolation ofmulti-terminal dc grids.Formulti-terminal dc grids that transmit power through overhead lines,HCBs are required to have reclosing capability due to the high fault probability and the fact that most of the faults are temporary faults.To avoid the secondary fault strike and equipment damage that may be caused by the reclosing of the HCB when the permanent fault occurs,an adaptive reclosing scheme based on traveling wave injection is proposed in this paper.The scheme injects traveling wave signal into the fault dc line through the additionally configured auxiliary discharge branch in the HCB,and then uses the reflection characteristic of the traveling wave signal on the dc line to identify temporary and permanent faults,to be able to realize fast reclosing when the temporary fault occurs and reliably avoid reclosing after the permanent fault occurs.The test results in the simulation model of the four-terminal dc grid show that the proposed adaptive reclosing scheme can quickly and reliably identify temporary and permanent faults,greatly shorten the power outage time of temporary faults.In addition,it has the advantages of easiness to implement,high reliability,robustness to high-resistance fault and no dead zone,etc.展开更多
The large-scale development of wind power is an important means to reduce greenhouse gas emissions, alleviate environmental pollution and improve the utilization rate of renewable energy. At the same time, large-scale...The large-scale development of wind power is an important means to reduce greenhouse gas emissions, alleviate environmental pollution and improve the utilization rate of renewable energy. At the same time, large-scale non grid connected wind power generation theory avoids the technical difficulties of wind power integration [1]. However, due to the randomness and uncontrollability of wind energy, the output power of the wind power generation system will fluctuate accordingly [2]. Therefore, the corresponding energy storage devices are arranged in the non-grid-connected wind power generation system to ensure the power quality, and it has become the key to full utilization of renewable energy. In the case of wind speed fluctuation, the DC bus control strategy of the wind turbine is proposed in this paper. It can reduce the impact on the unit converter and the power load;this ensures safe and stable operation of non-grid connected wind turbines.展开更多
China Southern Power Grid is a unique EHV AC/DC hybrid transmission network that operates in China. In its service area, the distribution of energy resources and the development of economy are extremely unbalanced, so...China Southern Power Grid is a unique EHV AC/DC hybrid transmission network that operates in China. In its service area, the distribution of energy resources and the development of economy are extremely unbalanced, so long-distance and bulk power transmission are needed; besides, the geography and climate conditions are serious, rains, fogs, lightning and typhoon as well as high temperature are common all the year round. Facing these challenges, the power grid enhanced stability control, improved the equipment and strengthen the network structure. In the future, the power grid plans to optimize the disposition of power sources and build digitalized power system.展开更多
Among the factors determining the performance of the new renewable energy system, the processing part of the untreated DC power is a very important element. In fact, the area where the loss of the new renewable energy...Among the factors determining the performance of the new renewable energy system, the processing part of the untreated DC power is a very important element. In fact, the area where the loss of the new renewable energy system is greatest is also the DC transmission and distribution technology. It is critical to prevent this loss and to improve the performance of the system, and analyze the performance of the resulting through the application of the resulting algorithms. In this thesis, we are discussing ways to calibrate the error in the PV distribution system within the solar power generation system using the Bypass Line Configuration Algorithm. I would like to note that if the operation of the Bypass Line device generates electrical abnormalities in the system’s circuits, it can recover the performance of the system, thereby improving performance.展开更多
Nowadays, the DC distribution system has been suggested, as a replacement for the AC power distribution system with electric propulsion. This idea signifies a fresh approach of issuing energy for low-voltage installat...Nowadays, the DC distribution system has been suggested, as a replacement for the AC power distribution system with electric propulsion. This idea signifies a fresh approach of issuing energy for low-voltage installations. It can be used for any electrical application up to 20 MW and works at a nominal voltage of 1000 V DC. The DC distribution system is just an extension of the multiple DC links that previously available in all propulsion and thruster drives, which typically comprise more than 80% of the electrical power consumption on electric propulsion vessels. A fault detection and islanding scheme for DC grid connected PV system is presented in this paper. Unlike traditional ac distribution systems, protection has been challenging for dc systems. The goals of this paper are to classify and detect the fault in the PV system as well as DC grid and to isolate the faulted section so that the system keeps operating without disabling the entire system. The results show the measured values of power at PV panel and DC grid side under different fault condition, which indicates the type of fault that occurs in the system.展开更多
Over the last few years, smart grids have become a topic of intensive research, development and deployment across the world. This is due to the fact that, through the smart grid, stable and reliable power systems can ...Over the last few years, smart grids have become a topic of intensive research, development and deployment across the world. This is due to the fact that, through the smart grid, stable and reliable power systems can be achieved. This paper presents a fuzzy logic control for dual active bridge series resonant converters for DC smart grid application. The DC smart grid consists of wind turbine and photovoltaic generators, controllable and DC loads, and power converters. The proposed control method has been applied to the controllable load's and the grid side's dual active bridge series resonant converters for attaining control of the power system. It has been used for management of controllable load's state of charge, DC feeder's voltage stability during the loads and power variations from wind energy and photovoltaic generation and power flow management between the grid side and the DC smart grid. The effectiveness of the proposed DC smart grid operation has been verified by simulation results obtained by using MATLAB and PLECS cards.展开更多
A control strategy of repetitive control without inductorance decoupling was proposed to address the problem of high total harmonic distortion(THD)rate of the network-side current caused by the reduced stability of th...A control strategy of repetitive control without inductorance decoupling was proposed to address the problem of high total harmonic distortion(THD)rate of the network-side current caused by the reduced stability of the rectifier module of the DC charging pile under weak grid as well as the dead zone and nonlinearity of switching devices during charging.Firstly,the parallel repetitive control was constructed in the inner current loop,and the proportional-integral(PI)+repetitive controller based on parallel structure was designed.For system compensation,a second-order low-pass filter was selected to correct the system,and the network-side current harmonics were actively suppressed without increasing the filtering device,which effectively improves the quality of grid-connected current.Secondly,based on the synthetic vector method,the controller parameters were designed to realize the elimination of main pole by establishing two synchronous rotation coordinate system vector differential equations,so as to realize the inductanceless decoupling to cope with the influence of network-side inductance fluctuation on the stability of the control system under weak grid.By theoretical analysis and simulation,the proposed control strategy was embedded into the self-developed digital signal processor for the rectifier module of DC charging pile,simulated dynamic and steady-state operation experiments were conducted,and comparative analysis was performed to prove the feasibility of the proposed control strategy.展开更多
随着基于电压源型换流器的柔性直流输电(voltage source converter based high voltage direct current,VSC-HVDC)技术的快速发展,十几年间世界范围内已建成数十个各种不同电压等级的VSC-HVDC工程。根据交流电网的发展历史,未来构建大...随着基于电压源型换流器的柔性直流输电(voltage source converter based high voltage direct current,VSC-HVDC)技术的快速发展,十几年间世界范围内已建成数十个各种不同电压等级的VSC-HVDC工程。根据交流电网的发展历史,未来构建大规模直流电网是必然趋势。然而直流电网必须采用DC/DC变换器来充当直流变压器的角色,因此高效率、低成本的高压大容量DC/DC变换器是直流电网技术中亟待攻克的关键基础性课题。该文针对不同电压等级直流输电线路互联的技术需求,对经典低压DC/DC拓扑进行改造,推演出一系列基于容性能量转移原理的高压大容量DC/DC变换器拓扑,并揭示此类拓扑的演化规律和换流原理。相比传统变换器方案,该拓扑可降低器件数量,提升拓扑转换效率以及减小变换器体积重量。最后,通过仿真和实验验证基于容性能量转移原理的DC/DC变换器的可行性。展开更多
基金supported by the National Natural Science Foundation of China(No.52277075)the State Key Laboratory of Advanced Power Transmission Technology(Grant No.GEIRI-SKL-2020-012).
文摘To ensure their sound and continuous operation to the greatest extent,VSC-based DC girds have extremely stringent requirements for transmission line relay protection.In terms of guaranteeing their reliability,accurate identification of lightning strikes on DC transmission lines is one of the urgent key problems to be solved.An effective ultra-high-speed identification scheme of lightning strikes suitable for the VSC-based DC grid is proposed in this paper.First,an 1-mode reverse voltage traveling wave(RVTW)is constructed applying the pole-mode transformation theory.Next,fault traveling wave propagation characteristics along the DC transmission line are analyzed in depth utilizing Peterson's law.Then,differences of time-frequency electromagnetic transient characteristics of 1-mode RVTWs between disturbances and faults caused by lightning strikes are distinguished in detail by means of the classical wavelet transformation multi-resolution analysis theory.Finally,extensive simulations are carried out to evaluate the performance of the proposed identification scheme,and by which its excellent rapidity,reliability and robustness are validated.Index Terms-Lightning-strike identification,Multi-resolution analysis,Relay protection,Traveling-wave protection,VsC-based DC grid,Wavelet transformation.
文摘Segmentation of large AC systems through DC links introduces a new concept that utilizes the advantages of direct current transmission to improve network reliability and increase power transfer capacity. Technical literature argues that the segmentation of the AC network and the introduction of DC links at these systems connection points bring benefits to system operation, once contingencies generated on one side of the DC connection point would not be reflected on the other side of DC connection, thereby reducing the likelihood of cascading shutdowns and blackouts due to load restraint on transmission lines and transformers. Amidst this scenario, this paper presents a study of the main topics regarding the use of this new network segmentation philosophy, bringing a practical point of view for the use of this concept at the electrical power system planning. The effect of DC segmentation before a contingency that would initiate major outages in an adapted electrical system model IEEE-14 bus is studied and simulations have been performed with test HVAC systems and segmented by HVDC link. The results have been compared, principally in relation to the voltage bus, reactive power generation, system losses and power flow at the lines, and demonstrated that this new concept improved the grid reliability.
基金supported by the Science and Technology Project of State Grid Corporation of China under Grant 520201210025。
文摘The hybrid dc circuit breaker(HCB)has the advantages of fast action speed and low operating loss,which is an idealmethod for fault isolation ofmulti-terminal dc grids.Formulti-terminal dc grids that transmit power through overhead lines,HCBs are required to have reclosing capability due to the high fault probability and the fact that most of the faults are temporary faults.To avoid the secondary fault strike and equipment damage that may be caused by the reclosing of the HCB when the permanent fault occurs,an adaptive reclosing scheme based on traveling wave injection is proposed in this paper.The scheme injects traveling wave signal into the fault dc line through the additionally configured auxiliary discharge branch in the HCB,and then uses the reflection characteristic of the traveling wave signal on the dc line to identify temporary and permanent faults,to be able to realize fast reclosing when the temporary fault occurs and reliably avoid reclosing after the permanent fault occurs.The test results in the simulation model of the four-terminal dc grid show that the proposed adaptive reclosing scheme can quickly and reliably identify temporary and permanent faults,greatly shorten the power outage time of temporary faults.In addition,it has the advantages of easiness to implement,high reliability,robustness to high-resistance fault and no dead zone,etc.
文摘The large-scale development of wind power is an important means to reduce greenhouse gas emissions, alleviate environmental pollution and improve the utilization rate of renewable energy. At the same time, large-scale non grid connected wind power generation theory avoids the technical difficulties of wind power integration [1]. However, due to the randomness and uncontrollability of wind energy, the output power of the wind power generation system will fluctuate accordingly [2]. Therefore, the corresponding energy storage devices are arranged in the non-grid-connected wind power generation system to ensure the power quality, and it has become the key to full utilization of renewable energy. In the case of wind speed fluctuation, the DC bus control strategy of the wind turbine is proposed in this paper. It can reduce the impact on the unit converter and the power load;this ensures safe and stable operation of non-grid connected wind turbines.
文摘China Southern Power Grid is a unique EHV AC/DC hybrid transmission network that operates in China. In its service area, the distribution of energy resources and the development of economy are extremely unbalanced, so long-distance and bulk power transmission are needed; besides, the geography and climate conditions are serious, rains, fogs, lightning and typhoon as well as high temperature are common all the year round. Facing these challenges, the power grid enhanced stability control, improved the equipment and strengthen the network structure. In the future, the power grid plans to optimize the disposition of power sources and build digitalized power system.
文摘Among the factors determining the performance of the new renewable energy system, the processing part of the untreated DC power is a very important element. In fact, the area where the loss of the new renewable energy system is greatest is also the DC transmission and distribution technology. It is critical to prevent this loss and to improve the performance of the system, and analyze the performance of the resulting through the application of the resulting algorithms. In this thesis, we are discussing ways to calibrate the error in the PV distribution system within the solar power generation system using the Bypass Line Configuration Algorithm. I would like to note that if the operation of the Bypass Line device generates electrical abnormalities in the system’s circuits, it can recover the performance of the system, thereby improving performance.
文摘Nowadays, the DC distribution system has been suggested, as a replacement for the AC power distribution system with electric propulsion. This idea signifies a fresh approach of issuing energy for low-voltage installations. It can be used for any electrical application up to 20 MW and works at a nominal voltage of 1000 V DC. The DC distribution system is just an extension of the multiple DC links that previously available in all propulsion and thruster drives, which typically comprise more than 80% of the electrical power consumption on electric propulsion vessels. A fault detection and islanding scheme for DC grid connected PV system is presented in this paper. Unlike traditional ac distribution systems, protection has been challenging for dc systems. The goals of this paper are to classify and detect the fault in the PV system as well as DC grid and to isolate the faulted section so that the system keeps operating without disabling the entire system. The results show the measured values of power at PV panel and DC grid side under different fault condition, which indicates the type of fault that occurs in the system.
文摘Over the last few years, smart grids have become a topic of intensive research, development and deployment across the world. This is due to the fact that, through the smart grid, stable and reliable power systems can be achieved. This paper presents a fuzzy logic control for dual active bridge series resonant converters for DC smart grid application. The DC smart grid consists of wind turbine and photovoltaic generators, controllable and DC loads, and power converters. The proposed control method has been applied to the controllable load's and the grid side's dual active bridge series resonant converters for attaining control of the power system. It has been used for management of controllable load's state of charge, DC feeder's voltage stability during the loads and power variations from wind energy and photovoltaic generation and power flow management between the grid side and the DC smart grid. The effectiveness of the proposed DC smart grid operation has been verified by simulation results obtained by using MATLAB and PLECS cards.
基金supported by National Natural Science Foundation of China(No.61903291)Shaanxi Province Key R&D Program(No.2022GY-134)。
文摘A control strategy of repetitive control without inductorance decoupling was proposed to address the problem of high total harmonic distortion(THD)rate of the network-side current caused by the reduced stability of the rectifier module of the DC charging pile under weak grid as well as the dead zone and nonlinearity of switching devices during charging.Firstly,the parallel repetitive control was constructed in the inner current loop,and the proportional-integral(PI)+repetitive controller based on parallel structure was designed.For system compensation,a second-order low-pass filter was selected to correct the system,and the network-side current harmonics were actively suppressed without increasing the filtering device,which effectively improves the quality of grid-connected current.Secondly,based on the synthetic vector method,the controller parameters were designed to realize the elimination of main pole by establishing two synchronous rotation coordinate system vector differential equations,so as to realize the inductanceless decoupling to cope with the influence of network-side inductance fluctuation on the stability of the control system under weak grid.By theoretical analysis and simulation,the proposed control strategy was embedded into the self-developed digital signal processor for the rectifier module of DC charging pile,simulated dynamic and steady-state operation experiments were conducted,and comparative analysis was performed to prove the feasibility of the proposed control strategy.
文摘随着基于电压源型换流器的柔性直流输电(voltage source converter based high voltage direct current,VSC-HVDC)技术的快速发展,十几年间世界范围内已建成数十个各种不同电压等级的VSC-HVDC工程。根据交流电网的发展历史,未来构建大规模直流电网是必然趋势。然而直流电网必须采用DC/DC变换器来充当直流变压器的角色,因此高效率、低成本的高压大容量DC/DC变换器是直流电网技术中亟待攻克的关键基础性课题。该文针对不同电压等级直流输电线路互联的技术需求,对经典低压DC/DC拓扑进行改造,推演出一系列基于容性能量转移原理的高压大容量DC/DC变换器拓扑,并揭示此类拓扑的演化规律和换流原理。相比传统变换器方案,该拓扑可降低器件数量,提升拓扑转换效率以及减小变换器体积重量。最后,通过仿真和实验验证基于容性能量转移原理的DC/DC变换器的可行性。