In this study, neutral salt spray accelerated corrosion test of copper–aluminium composite under 0–125 A DC current was carried out under 5% concentration. The effect of corrosion behaviour on copper–aluminium comp...In this study, neutral salt spray accelerated corrosion test of copper–aluminium composite under 0–125 A DC current was carried out under 5% concentration. The effect of corrosion behaviour on copper–aluminium composite by DC current was carried out by a scanning electron microscope(SEM) with energy-dispersive spectroscopy(EDS), X-ray diffraction(XRD) patterns, X-ray photoelectron spectroscopy(XPS), weight-loss method and electrochemical analysis. The results show that the current can accelerate the corrosion rate. Meanwhile, the current temperature effect can reduce the corrosion rate. The current caused directional migration of ions resulting in different corrosion products on positive and negative poles of specimen, and the corrosion degree on the positive pole was more serious. The galvanic corrosion mechanism at the copper–aluminium interface is different from the pitting corrosion mechanism far away from the interface, and the latter is more affected by DC current.展开更多
There are magnetic interference problems in the applications of DC current comparator. Analysis on the magnetic effectiveness which is applied by the external magnetic field is introduced in this paper. The effectiven...There are magnetic interference problems in the applications of DC current comparator. Analysis on the magnetic effectiveness which is applied by the external magnetic field is introduced in this paper. The effectiveness is proved by the actual results which are compared with the magnetic- circuit method and the finite element method. In addition, the reference comment is given which can be used in the practical work of DC current comparator shield design.展开更多
DC magnetic biasing problem,caused by the DC grounding electrode, threatened the safe operation of AC power grid. In this paper, the characteristics of the soil stratification near DC grounding electrode was researche...DC magnetic biasing problem,caused by the DC grounding electrode, threatened the safe operation of AC power grid. In this paper, the characteristics of the soil stratification near DC grounding electrode was researched. The AC-DC interconnected large-scale system model under the monopole operation mode was established. The earth surface potential and DC current distribution in various stations under the different surface thickness was calculated. Some useful conclusions are drawn from the analyzed results.展开更多
This paper focus on the Modeling and Calculation of DC current distribution in AC power grid induced under HVDC Ground-Return-Mode. Applying complex image method and boundary element method, a new field-circuit coupli...This paper focus on the Modeling and Calculation of DC current distribution in AC power grid induced under HVDC Ground-Return-Mode. Applying complex image method and boundary element method, a new field-circuit coupling model was set up. Based on the calculation result with complex image method, this paper derived the modification factor for induced earth potential from practical measurement, which increased the accuracy of calculation. The modification method is helpful for evaluation on the effect of means used for blocking the dc-bias current in transformer neutral and also useful for the forecast of the DC current distribution when the power grid is in different line connection mode. The DC distribution character in Guangdong power grid is shown and suggestion is proposed that the mitigation of dc-bias should start from those substations whose earth-potential is highest.展开更多
To miniaturize a very low level dc current amplifier and to improve its output response speed, the switched capacitor negative feedback circuit (SCNF), instead of the conventionally used high-ohmage resistor, is prese...To miniaturize a very low level dc current amplifier and to improve its output response speed, the switched capacitor negative feedback circuit (SCNF), instead of the conventionally used high-ohmage resistor, is presented in this paper. In our system, a switched capacitor filter (SCF) and an offset controller are also used to decrease vibrations and offset voltage at the output of the amplifier using SCNF. The theoretical output voltage of the very low level dc current amplifier using SCNF is obtained. The experimental results show that the unnecessary components of the amplifier’s output are much decreased, and that the response speed of the amplifier with both the SCNF and SCF is faster than that using high-ohmage resistor.展开更多
This paper describes a very low level dc current amplifier using switched capacitor (SC) circuit to miniaturize and improve its output response speed, instead of the conventionally used high-oh-mage resistor. A switch...This paper describes a very low level dc current amplifier using switched capacitor (SC) circuit to miniaturize and improve its output response speed, instead of the conventionally used high-oh-mage resistor. A switched capacitor filter (SCF) and an offset controller are also used to decrease vibrations and offset voltage at the output of the amplifier. The simulation results show that the parasitic capacitances that are distributed to the input portion of the amplifier have some effect on offset voltage. From the experimental results, it is seen that the duty ratio of the clock cycle of SC circuit should be in the range from 0.05 to 0.70. It is suggested that the proposed very low level dc current amplifier using SC circuit is an effective way to obtain both a faster output response and its miniaturization.展开更多
This paper proposes the design of a novel DC current flow controller(CFC)and evaluates the control performance of balancing and regulating the DC branch currents using the DC CFC in a meshed multi-terminal HVDC(MTDC)g...This paper proposes the design of a novel DC current flow controller(CFC)and evaluates the control performance of balancing and regulating the DC branch currents using the DC CFC in a meshed multi-terminal HVDC(MTDC)grid.The DC CFC consists of two identical full bridge DC-DC converters with the capacitors of the two converters being connected in parallel.The scalability of the DC CFC is easily achievable due to the identical bridge converter topology;the cost of this DC CFC is also relatively low due to its simple physical structure and low voltage ratings.The control performance of the DC CFC is tested on a meshed 3-terminal(3-T)HVDC grid,which is based on modular multilevel converters(MMC).The DC branch current control in the meshed MTDC grid is achieved using the proposed control strategy of the DC CFC,and is verified through case studies on the real-time digital simulator(RTDS).展开更多
For the safe and fast recovery of line commutated converter based high-voltage direct current(LCC-HVDC)transmission systems after faults,a DC current order optimization based strategy is proposed.Considering the const...For the safe and fast recovery of line commutated converter based high-voltage direct current(LCC-HVDC)transmission systems after faults,a DC current order optimization based strategy is proposed.Considering the constraint of electric and control quantities,the DC current order with the maximum active power transfer is calculated by Thevenin equivalent parameters(TEPs)and quasi-state equations of LCC-HVDC transmission systems.Meanwhile,to mitigate the subsequent commutation failures(SCFs)that may come with the fault recovery process,the maximum DC current order that avoids SCFs is calculated through imaginary commutation process.Finally,the minimum value of the two DC current orders is sent to the control system.Simulation results based on PSCAD/EMTDC show that the proposed strategy mitigates SCFs effectively and exhibits good performance in recovery.展开更多
Controllability of DC current/power flow is essentialin multi-terminal HVDC (MTDC) grids, particularly for theMTDC grids in a meshed topology. In this paper, consideringmeshed MTDC (M2TDC) grids with the installation ...Controllability of DC current/power flow is essentialin multi-terminal HVDC (MTDC) grids, particularly for theMTDC grids in a meshed topology. In this paper, consideringmeshed MTDC (M2TDC) grids with the installation of twoline/multi-lineDC current flow controllers (CFCs), a small-signalmodel of the DC CFCs integrated M2TDC grids is derived,studying the impact of the power losses of the DC CFC andtheir influence on the analysis of energy exchanges. The systemstability analysis is analysed using the Nyquist diagram, which ismore suitable for analyzing complex nonlinear systems with morecompact and reliable indicators of stability in comparison withgain/phase margins shown in the Bode diagram. In addition, aselection method of the interconnected capacitor of the DC CFCis proposed under different operating conditions. The impact ofthe switching frequencies of the DC CFC on the control ranges ofthe DC current flows is analyzed. The effectiveness of the Nyquistanalysis and the capacitance selection method is verified bysimulation studies using PSCAD/EMTDC. The obtained control ranges of the DC CFC with different switching frequenciesand capacitances would be useful for practical engineeringapplications.展开更多
柔性直流电网的故障检测与保护研究是当前电力领域的关键技术。直流电网发生故障时,故障电流迅速上升导致电网系统设备损坏且稳定性下降,因此对故障保护系统的快速性和可靠性要求极高。通过比较线路上限流电感电压值在故障前后的变化,...柔性直流电网的故障检测与保护研究是当前电力领域的关键技术。直流电网发生故障时,故障电流迅速上升导致电网系统设备损坏且稳定性下降,因此对故障保护系统的快速性和可靠性要求极高。通过比较线路上限流电感电压值在故障前后的变化,提出一种利用限流电感两端电压比值实现线路故障识别的方法。在PSCAD/EMTDC仿真平台建立四端模块化多电平换流器型柔性直流输电(modular multilevel converter high voltage direct current,MMC-HVDC)电网模型,对所提出的方法进行故障启动、类型识别和极线选择验证。在故障被正确识别后,相应的直流断路器(DC circuit breaker,DCCB)能够正确动作并隔离故障。此外,还对系统的性能指标以及故障过渡电阻值、故障后系统的噪声、故障距离和通信误差方面因素进行可行性分析。研究结果表明,所提出的故障保护方案能够准确识别并且快速隔离故障,从而保障电网安全稳定运行。展开更多
基金financially supported by the National Natural Science Foundation of China(No.U1604251)the Doctoral Start-up Foundation of Liaoning Province(No.2019-BS-178)the National Outstanding Youth Science Fund Project of National Natural Science Foundation of China(CN)(No.U52001216)。
文摘In this study, neutral salt spray accelerated corrosion test of copper–aluminium composite under 0–125 A DC current was carried out under 5% concentration. The effect of corrosion behaviour on copper–aluminium composite by DC current was carried out by a scanning electron microscope(SEM) with energy-dispersive spectroscopy(EDS), X-ray diffraction(XRD) patterns, X-ray photoelectron spectroscopy(XPS), weight-loss method and electrochemical analysis. The results show that the current can accelerate the corrosion rate. Meanwhile, the current temperature effect can reduce the corrosion rate. The current caused directional migration of ions resulting in different corrosion products on positive and negative poles of specimen, and the corrosion degree on the positive pole was more serious. The galvanic corrosion mechanism at the copper–aluminium interface is different from the pitting corrosion mechanism far away from the interface, and the latter is more affected by DC current.
文摘There are magnetic interference problems in the applications of DC current comparator. Analysis on the magnetic effectiveness which is applied by the external magnetic field is introduced in this paper. The effectiveness is proved by the actual results which are compared with the magnetic- circuit method and the finite element method. In addition, the reference comment is given which can be used in the practical work of DC current comparator shield design.
文摘DC magnetic biasing problem,caused by the DC grounding electrode, threatened the safe operation of AC power grid. In this paper, the characteristics of the soil stratification near DC grounding electrode was researched. The AC-DC interconnected large-scale system model under the monopole operation mode was established. The earth surface potential and DC current distribution in various stations under the different surface thickness was calculated. Some useful conclusions are drawn from the analyzed results.
文摘This paper focus on the Modeling and Calculation of DC current distribution in AC power grid induced under HVDC Ground-Return-Mode. Applying complex image method and boundary element method, a new field-circuit coupling model was set up. Based on the calculation result with complex image method, this paper derived the modification factor for induced earth potential from practical measurement, which increased the accuracy of calculation. The modification method is helpful for evaluation on the effect of means used for blocking the dc-bias current in transformer neutral and also useful for the forecast of the DC current distribution when the power grid is in different line connection mode. The DC distribution character in Guangdong power grid is shown and suggestion is proposed that the mitigation of dc-bias should start from those substations whose earth-potential is highest.
文摘To miniaturize a very low level dc current amplifier and to improve its output response speed, the switched capacitor negative feedback circuit (SCNF), instead of the conventionally used high-ohmage resistor, is presented in this paper. In our system, a switched capacitor filter (SCF) and an offset controller are also used to decrease vibrations and offset voltage at the output of the amplifier using SCNF. The theoretical output voltage of the very low level dc current amplifier using SCNF is obtained. The experimental results show that the unnecessary components of the amplifier’s output are much decreased, and that the response speed of the amplifier with both the SCNF and SCF is faster than that using high-ohmage resistor.
文摘This paper describes a very low level dc current amplifier using switched capacitor (SC) circuit to miniaturize and improve its output response speed, instead of the conventionally used high-oh-mage resistor. A switched capacitor filter (SCF) and an offset controller are also used to decrease vibrations and offset voltage at the output of the amplifier. The simulation results show that the parasitic capacitances that are distributed to the input portion of the amplifier have some effect on offset voltage. From the experimental results, it is seen that the duty ratio of the clock cycle of SC circuit should be in the range from 0.05 to 0.70. It is suggested that the proposed very low level dc current amplifier using SC circuit is an effective way to obtain both a faster output response and its miniaturization.
基金supported by UK-China Smart Grid Project ERIFT via UK EPSRC,University of Birmingham SiGuang Li Scholarship and China Scholarship Council。
文摘This paper proposes the design of a novel DC current flow controller(CFC)and evaluates the control performance of balancing and regulating the DC branch currents using the DC CFC in a meshed multi-terminal HVDC(MTDC)grid.The DC CFC consists of two identical full bridge DC-DC converters with the capacitors of the two converters being connected in parallel.The scalability of the DC CFC is easily achievable due to the identical bridge converter topology;the cost of this DC CFC is also relatively low due to its simple physical structure and low voltage ratings.The control performance of the DC CFC is tested on a meshed 3-terminal(3-T)HVDC grid,which is based on modular multilevel converters(MMC).The DC branch current control in the meshed MTDC grid is achieved using the proposed control strategy of the DC CFC,and is verified through case studies on the real-time digital simulator(RTDS).
基金supported by the National Key Research and Development Program of China(No.2021YFB2400902)the Innovation Young Talents Program of Changsha Science and Technology Bureau(No.kq2107005)the Postgraduate Scientific Research Innovation Project of Hunan Province(No.QL20210101).
文摘For the safe and fast recovery of line commutated converter based high-voltage direct current(LCC-HVDC)transmission systems after faults,a DC current order optimization based strategy is proposed.Considering the constraint of electric and control quantities,the DC current order with the maximum active power transfer is calculated by Thevenin equivalent parameters(TEPs)and quasi-state equations of LCC-HVDC transmission systems.Meanwhile,to mitigate the subsequent commutation failures(SCFs)that may come with the fault recovery process,the maximum DC current order that avoids SCFs is calculated through imaginary commutation process.Finally,the minimum value of the two DC current orders is sent to the control system.Simulation results based on PSCAD/EMTDC show that the proposed strategy mitigates SCFs effectively and exhibits good performance in recovery.
基金National Natural Science Foundation of China under Grant 51807091Natural Science Foundation of Jiangsu Province BK20180478+1 种基金the China Postdoctoral Science Foundation under Grant 2019M661846EPSRC under Grant EP/N032888/1.
文摘Controllability of DC current/power flow is essentialin multi-terminal HVDC (MTDC) grids, particularly for theMTDC grids in a meshed topology. In this paper, consideringmeshed MTDC (M2TDC) grids with the installation of twoline/multi-lineDC current flow controllers (CFCs), a small-signalmodel of the DC CFCs integrated M2TDC grids is derived,studying the impact of the power losses of the DC CFC andtheir influence on the analysis of energy exchanges. The systemstability analysis is analysed using the Nyquist diagram, which ismore suitable for analyzing complex nonlinear systems with morecompact and reliable indicators of stability in comparison withgain/phase margins shown in the Bode diagram. In addition, aselection method of the interconnected capacitor of the DC CFCis proposed under different operating conditions. The impact ofthe switching frequencies of the DC CFC on the control ranges ofthe DC current flows is analyzed. The effectiveness of the Nyquistanalysis and the capacitance selection method is verified bysimulation studies using PSCAD/EMTDC. The obtained control ranges of the DC CFC with different switching frequenciesand capacitances would be useful for practical engineeringapplications.
文摘柔性直流电网的故障检测与保护研究是当前电力领域的关键技术。直流电网发生故障时,故障电流迅速上升导致电网系统设备损坏且稳定性下降,因此对故障保护系统的快速性和可靠性要求极高。通过比较线路上限流电感电压值在故障前后的变化,提出一种利用限流电感两端电压比值实现线路故障识别的方法。在PSCAD/EMTDC仿真平台建立四端模块化多电平换流器型柔性直流输电(modular multilevel converter high voltage direct current,MMC-HVDC)电网模型,对所提出的方法进行故障启动、类型识别和极线选择验证。在故障被正确识别后,相应的直流断路器(DC circuit breaker,DCCB)能够正确动作并隔离故障。此外,还对系统的性能指标以及故障过渡电阻值、故障后系统的噪声、故障距离和通信误差方面因素进行可行性分析。研究结果表明,所提出的故障保护方案能够准确识别并且快速隔离故障,从而保障电网安全稳定运行。