期刊文献+
共找到2篇文章
< 1 >
每页显示 20 50 100
Directional Overcurrent Relays Coordination Restoration by Reducing Minimum Fault Current Limiter Impedance
1
作者 Saadoun Abdel Aziz Mostafa DoaaKhalil Ibrahim Essam El-Din Abo El-Zahab 《Journal of Energy and Power Engineering》 2014年第6期1132-1141,共10页
FCL (fault current limiter) is used to solve relays miscoordination problem arises from DG (distributed generation) installation. In most published researches, different optimization methods are developed to obtai... FCL (fault current limiter) is used to solve relays miscoordination problem arises from DG (distributed generation) installation. In most published researches, different optimization methods are developed to obtain optimal relay settings to achieve coordination in case of not installing DG, then depending on the achieved optimal obtained relay settings, FCL impedance is deduced to ensure relays coordination restoration in case of installing DG. Based on original optimal relay settings, obtained FCL impedance is not the minimum one required to achieve relay coordination. The contribution of this paper is the generation of multi sets of original relay settings that increase the possibility of finding FCL impedance of minimum value which is lower than the calculated value based on original optimal relay settings. The proposed method achieves better economic target by reducing FCL impedance. The proposed approach is implemented and tested on IEEE-39 bus test system. 展开更多
关键词 FCL (fault current limiter) IP (pickup current setting relays coordination TDS (time-dial setting).
在线阅读 下载PDF
Finite Control Set Model Predictive Current Control of a Five-Phase PMSM with Virtual Voltage Vectors and Adaptive Control Set 被引量:9
2
作者 Wusen Wang Ying Fan +1 位作者 Siyu Chen Qiushi Zhang 《CES Transactions on Electrical Machines and Systems》 2018年第1期136-141,共6页
This paper presents an improved finite control set model predictive current control(FCS-MPCC)of a five-phase permanent magnet synchronous motor(PMSM).First,to avoid including all the 32 voltage vectors provided by a t... This paper presents an improved finite control set model predictive current control(FCS-MPCC)of a five-phase permanent magnet synchronous motor(PMSM).First,to avoid including all the 32 voltage vectors provided by a two-level five-phase inverter into the control set,virtual voltage vectors are adopted.As the third current harmonics can be much reduced by virtual voltage vectors automatically,the harmonic items in the cost function of conventional FCS-MPCC are not considered.Furthermore,an adaptive control set is proposed based on voltage prediction.Best control set with proper voltage vector amplitude corresponding to different rotor speed can be achieved by this method.Consequently,current ripples can be largely reduced and the system performs much better.At last,simulations are established to verify the steady and transient performance of the proposed FCS-MPCC,and experiments based on a 2 kW five-phase motor are carried out.The results have validated the performance improvement of the proposed control strategy. 展开更多
关键词 Adaptive control set current ripple finite control set model predictive current control(FCS-MPCC) permanent magnet synchronous motor(PMSM) virtual voltage vectors
在线阅读 下载PDF
上一页 1 下一页 到第