Aiming at the challenge of complex load balancing coordination for a three-phase four-leg(3P4L)based multi-ended low voltage flexible DC distribution system(M-LVDC)considering unbalanced power compensation,this paper ...Aiming at the challenge of complex load balancing coordination for a three-phase four-leg(3P4L)based multi-ended low voltage flexible DC distribution system(M-LVDC)considering unbalanced power compensation,this paper proposes a phase-split power decoupling unbalanced compensation strategy based load balancing strategy for 3P4L based M-LVDC.Firstly,the topology and operation principle of the 3P4L-based M-LVDC system is introduced,and quasi-proportional resonant(QPR)based phase-split power current control for the 3P4L converter is proposed.Secondly,a load-balancing control strategy considering unbalanced compensation for 3P4L-based MLVDC is presented,in which the control diagrams for each 3P4L-based converter are detailed.The core idea of the proposed strategy is to comprehensively consider the imbalance compensation and load rate balancing between the two areas to calculate the split-phase power and current reference values of each 3P4L converter and achieve the static error-free tracking of the reference values through the QPR current inner-loop control.These reference values are then tracked with zero steady-state error using QPR current inner-loop control.Finally,the effectiveness of the proposed control strategy is verified through a 3P4L M-LVDC case study conducted on the PSCAD/EMTDC software.Theresults indicate that the proposed method not only can reduce the three-phase imbalance degrees from>20% to<0.5%,but also achieve excellent balanced load rates,with the load-rate difference smaller than 1.5%.展开更多
基金supported by the key technology project of China Southern Power Grid Corporation(GZKJXM20220041)partly by theNational Key Research and Development Plan(2022YFE0205300).
文摘Aiming at the challenge of complex load balancing coordination for a three-phase four-leg(3P4L)based multi-ended low voltage flexible DC distribution system(M-LVDC)considering unbalanced power compensation,this paper proposes a phase-split power decoupling unbalanced compensation strategy based load balancing strategy for 3P4L based M-LVDC.Firstly,the topology and operation principle of the 3P4L-based M-LVDC system is introduced,and quasi-proportional resonant(QPR)based phase-split power current control for the 3P4L converter is proposed.Secondly,a load-balancing control strategy considering unbalanced compensation for 3P4L-based MLVDC is presented,in which the control diagrams for each 3P4L-based converter are detailed.The core idea of the proposed strategy is to comprehensively consider the imbalance compensation and load rate balancing between the two areas to calculate the split-phase power and current reference values of each 3P4L converter and achieve the static error-free tracking of the reference values through the QPR current inner-loop control.These reference values are then tracked with zero steady-state error using QPR current inner-loop control.Finally,the effectiveness of the proposed control strategy is verified through a 3P4L M-LVDC case study conducted on the PSCAD/EMTDC software.Theresults indicate that the proposed method not only can reduce the three-phase imbalance degrees from>20% to<0.5%,but also achieve excellent balanced load rates,with the load-rate difference smaller than 1.5%.