摘要 在生产过程中,有些电容式变送器出现输出为零的现象,影响到参数的测量或过程控制。通过生产现场的诊断和实验室测试,查出了产生该故障的部位。运用电容式变送器的工作原理,分析出了产生该故障的原因。该故障是由于传感器测量膜片或隔离膜片的弹性模量发生变化而引起的。介绍了消除这种故障的具体办法,并用此方法解决了多台电容式变送器的故障,取得了较好的经济效益。因而这种故障的消除方法具有一定的实用推广价值。 In production process, there is the phenomenon that the output showing zero appears with some capacitancetype signaltransformers, which influences parameter measurement or process control. By spot detection and tests in the lab, the fault part has been found out. And by making use of the functioning theory of capacitancetype signaltransformers, it is analysed that the fault is caused by the changes of the sensor's measuring diaphragm or segregating diaphragm. Furthermore, the specific approaches to dispose of the fault has been gotten. In practice, it helps fix the breakdown of several capacitancetype signaltransformers by applying those approaches and has got not bad economic benefit. Therefore the approaches to dispose of this kind of fault are worth spreading in application.
出处 《控制工程》 CSCD 2003年第6期495-496,554,共3页 Control Engineering of China
关键词 电容式变送器 隔离膜片 电路原理图 故障诊断 故障处理 工业自动化仪表 signal-transformer measuring diaphragm segregating diaphragm fault
  • 相关文献

参考文献2

  • 1俞茂宏 汪惠雄.材料力学[M].北京:高等教育出版社,1987..
  • 2吴永生 等.热工测试及仪表[M].北京:水利出版社,1981..

共引文献2

同被引文献5

  • 1马场清太郎.运算放大器应用电路设计[M].北京:科学出版社,2007.
  • 2扬振江 等.智能仪器与数据采集系统中的新器件及应用[M].西安:西安电子科技大学出版社,2001..
  • 3扬振江,孙占彪,王曙梅,等.智能仪器与数据采集系统中的新器件及应用[M].西安:西安电子科技大学出版社,2001.
  • 4李建军,薛宁.液氧平均流量测量研究[J].火箭推进,2010,36(1):67-70. 被引量:5
  • 5李正兵,蒋兴加,王小丽.高精度新型调制变送器设计与应用[J].火箭推进,2011,37(5):69-73. 被引量:12